31-5000573 Rev. 2 17
ENGLISH
INSTALLATION INSTRUCTIONS
Pipe Specification
1. Pipe “A” diameter (between indoor and branch pipe) (depends on indoor pipe)
Indoor kbtu/h Gas pipe in(mm) Liquid pipe in(mm)
5 3/8(9.52) 1/4(6.35)
7~18 1/2(12.7) 1/4(6.35)
24~54 5/8(15.88) 3/8(9.52)
72 1-1/8(28.58) 3/8(9.52)
96 1-1/8(28.58) 1-1/8(28.58)
NOTES:
As stands for high wall indoor units:
• AS072, AS092 gas pipe / liquid pipe: Ø1/2(12.7mm) / Ø1/4(6.35mm).
• AS182 gas pipe / liquid pipe: Ø5/8(15.88mm) / Ø3/8(9.52mm).
Ïõòð÷ëèìñçòòõ÷ò÷ëèöëòõ÷èö÷åõäñæëóìóè$)#$é÷¤!%ð¥óïèäöèæëäñêèöóèæìéìæä÷ìòñöòéóìóèäöóèõ÷ëè÷äåïèåèïòú
The first branch pipe
Outdoor gather pipe
aaa
b
d
d
e
ggg
Outdoor
Unit
Outdoor
Unit
Outdoor
Unit
f
f
b
d
d
d
aa
ccc
d
VP4
VP4
VP1
VP1 VP1
aaaa
aaa
b
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
aaa
aa
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
àëèñõä÷èçõèéõìêèõä÷ìñê!(îå÷ø¦ë¤%#îà¥æëäêèöóèæìéìæä÷ìòñöòéêäöóìóè¦ïìôøìçóìóè÷òļ%¦(¤!%((ðð¥¦
Ø3/8(9.52mm).
When18kbtu/h (5.3kW) < rated refrigerating < 57.3kbtu/h(16.8KW), change specifications of gas pipe / liquid
pipe to Ø3/4(19.05mm) / Ø3/8(9.52mm).
When rated refrigerating < 57.3kbtu/h(16.8KW), change specification of liquid pipe to Ø1/2(12.7mm).