Tripp Lite MBP6K208 Eaton 9PX Maintenance Bypass for Select 5kVA to 6kVA 9PX UPS Systems, Hardwired Input/Output, 2 L6-30R Outlets, 3U Rack/Tower

Installation and user manual - Page 44

For MBP6K208. Also, The document are for others Tripp Lite models: 9PX 700 RT, 9PX 1000 RT, 9PX 1000GRT, 9PX 1500 RT, 9PX 1500GRT, 9PX 2000 RT, 9PX 2200 GRT, 9PX 3000 RT, 9PX 3000 GRT, 9PX 3000 GLRT, 9PX EBM 36V RT, 9PX EBM 48V RT, 9PX EBM 72V RT

PDF File Manual, 46 pages, Read Online | Download pdf file

Loading ...
Loading ...
Loading ...
Page 44
9PX 1-3 KVA US_EN
Table 8. Environmental and safety
Certifications
IEC/EN 62040-1
IEC/EN 62040-2 : Cat. C1
IEC/EN 62040-3
UL1778 5th edition
CSA 22.2
EMC (Emissions)*
CISPR22 Class B
FCC part 15 Class B / ICES-003
EMC (Immunity)
IEC 61000-4-2, (ESD): 8 kV Contact Discharge / 15 kV Air Discharge
IEC 61000-4-3, (Radiated field): 10 V/m
IEC 61000-4-4, (EFT): Power (Coupling network) 4 kV / Ethernet (Coupling
clamp) 2 kV
IEC 61000-4-5, (Surges): 2 kV Differentiel Mode / 4 kV Common Mode /
1 kV Ethernet
IEC 61000-4-6, (Electromagnetic field): 10 V
IEC 61000-4-8, (Conducted magnetic field): 30 A/m
* for output cable < 10m.
Agency markings* CE / cULus / NOM / Energy Star / BSMI
Operating temperature 0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude
Note: thermal protection switches load to Bypass in case of overheating.
Storage temperature 0 to 40°C (32 to 104°F) with batteries
-25 to 55°C (-13 to 130°F) without batteries
Transit temperature -25 to 55°C (-13 to 130°F)
Relative humidity 0 to 96% no condensing
Operating altitude Up to 3,000 meters (9,843 ft) above sea level, no derating for 35°c (95°F)
room temperature
Transit altitude Up to 10,000 meters (32,808 ft) above sea level
Audible noise < 47 dBA at 1 meter typical for 2K et 3K models
< 40 dBA at 1 meter typical for 70, 1K et 1K5 models
* 9PX1000GRT, 9PX 1500GRT, 9PX2200GRT, 9PX3000GRT, 9PX3000GLRT have CE/ cULus/Energy Star/
BSMI.
9PXEBM36RT, 9PXEBM48RT, 9PXEBM72RT have CE / cULus / NOM.
Table 9. Battery
Internal batteries EBM
Rack / Tower
configuration
700VA: 36Vdc - 3 x 12V, 9Ah
1000VA LV: 36Vdc - 3 x 12V, 9Ah
1000VA HV :48Vdc - 4 x 12V, 7Ah
1500VA: 48Vdc - 4 x 12V, 9Ah
2200VA: 72Vdc - 6 x 12V, 7Ah
3000VA: 72Vdc - 6 x 12V, 9Ah
9PXEBM36RT: 36Vdc - 2 x 3 x 12V, 7Ah
9PXEBM48RT: 48Vdc - 2 x 4 x 12V, 9Ah
9PXEBM72RT: 72Vdc - 2 x 6 x 12V, 9Ah
Type Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year
float service life at 25°C (77°F). Lifetime is reduced above 25°C (77°F).
Monitoring Advanced monitoring for earlier failure detection and warning
EBM battery cable
length
350 mm / 13.78 in
8. Specifications