Tripp Lite MBP6K208 Eaton 9PX Maintenance Bypass for Select 5kVA to 6kVA 9PX UPS Systems, Hardwired Input/Output, 2 L6-30R Outlets, 3U Rack/Tower

Installation and user manual - Page 14

For MBP6K208. Also, The document are for others Tripp Lite models: 9PX 700 RT, 9PX 1000 RT, 9PX 1000GRT, 9PX 1500 RT, 9PX 1500GRT, 9PX 2000 RT, 9PX 2200 GRT, 9PX 3000 RT, 9PX 3000 GRT, 9PX 3000 GLRT, 9PX EBM 36V RT, 9PX EBM 48V RT, 9PX EBM 72V RT

PDF File Manual, 46 pages, Read Online | Download pdf file

Loading ...
Loading ...
Loading ...
Page 14
9PX 1-3 KVA US_EN
2. Presentation
Submenu Available settings Default settings
In/Out settings
Output voltage [100V] [110V] [120V] [125V]
[200V] [208V] [220V] [230V] [240V]
[120V]
[208V]
Output frequency Mode: [Normal] [Converter] [Marine]
Frequency can be changed in
Frequency [Converter] mode
In [Marine] mode output frequency
follows input frequency
[Normal]
Output mode Mode: [Industrial] [IT] [Custom]
Overload: [Inv>Stop] [Inv>BP]
[Inv>BP>Inv]
Short-circuit: [Inv>Stop] [Inv>BP]
[Inv>BP>Inv]
[IT]
[Inv>BP>Inv]
[Inv>Stop]
Input volt hysteresis Sets input voltage hysteresis
from [1] to |10V]
[10V]
High Efficiency
mode
[Enabled] [Disabled]
Power the output from Bypass for high
efficiency
[Disabled]
Bypass settings
[Volt low]
[Volt high]
[Qualify]
[Hz synch]
[Unsynch]
[80V] LV; [160V] HV;
[144V] LV; [276V] HV;
[In spec];
[5%];
[Half cycle]
Load segments
[Auto start delay]
[Auto shutdown delay]
UPS: [0s]; Group1: [3s];
Group2: [6s]
UPS: [Disabled];
Group1: [Disabled];
Group2: [Disabled]
Overload
prealarm
[10%] … [102%]
Load % when overload alarm occurs
[102%]
On/Off settings
Start/Restart [Cold start] [Auto restart] [Auto start]
[Start on bypass]
[Cold start] [Auto restart] are
Enabled
[Auto start] [Start on bypass]
are Disabled
Forced reboot [Enabled] [Disabled]
[Timer] [10s] … [180s]
When mains recover during a
shutdown sequence:
If set to Enabled, shutdown sequence
will complete and wait 10 seconds
prior to restart,
If set to Disabled, shutdown sequence
will not complete, UPS stays on.
[Enabled]
[10s]
Energy saving [Enabled] [Disabled]
[Timer] [1min] … [15min]
[Level] [100W] … [1000W]
If Enabled, UPS will shut-down after
defined duration. of back-up time, if
load is less than set value.
[Disabled]
[5min]
[100W]
Sleep mode [Enabled] [Disabled]
[Timer] [10min] … [120min]
If Disabled, LCD and communication
will turn OFF immediately after UPS is
OFF.
If Enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
[Enabled]
[90min]
Site wiring fault [Enabled] [Disabled]
Prevents from starting the UPS in case
of phase vs neutral wires swapping.
[Disabled]
Power Off alert [Enabled] [Disabled]
If Enabled, activates a confirmation
screen that requires user confirmation
after pressing the power button,
before the UPS shutdown occurs.
[Enabled]
Loading ...
Loading ...
Loading ...