9PX 1-3 KVA US_EN
6. UPS maintenance
6.5 Replacing the UPS equipped with a HotSwap MBP
The HotSwap MBP module makes it
possible to service or even replace
the UPS without affecting the connected
loads.
Maintenance
1. Set switch
33
to Bypass position.
The red LED on the HotSwap MBP
module goes ON, indicating that the
load is supplied directly with AC input
source power.
2. Stop the UPS by pressing the
button on the UPS control panel.
LED
31
"UPS ON - OK to switch"
goes OFF, the UPS can now be
disconnected and replaced.
Return to normal operation
1. Check that the UPS is correctly
connected to the HotSwap MBP
module.
2. Start the UPS by pressing the
button on the UPS control panel.
LED
31
"UPS ON - OK to switch" on
the HotSwap MBP module goes ON
(otherwise, there is a connection error
between the HotSwap MBP module
and the UPS).
3. Set switch
33
to Normal position.
The red LED on the HotSwap MBP
module goes OFF.
6.6 Recycling the used equipment
Contact your local recycling or hazardous waste center for information on proper disposal of the used
equipment.
• Donotdisposeofthebatteryorbatteriesinare.Batteriesmayexplode.Properdisposalofbatte-
ries is required. Refer to your local codes for disposal requirements.
• Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes.
It may be toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead acid
batteries and must be disposed of properly. For more information, contact your local recycling/
reuse or hazardous waste center.
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal,
contact your local recycling/reuse or hazardous waste center.
MBP-120