8. Specifications
Table 6. Electrical output
All models
Normal mode Efficiency mode Battery mode
Voltage regulation
±1% ±2%
Efficiency
89.9% for 700 LV models
90.3% for 1K LV models
90.2% for 1K G models
90.0% for 1.5K LV models
91% for 1.5K G models
91.4% for 2K LV models
93% for 2K G models
94% for 3K G models
95.3% for 700 LV models
95.8% for 1K LV models
96% for 1K G models
95.8% for 1K5 LV models
96.5% for 1.5K G models
96.8% for 2K LV models
98% for 2K G models
97.2% for 3K LV models
98% for 3K G models
83% for 700 LV models
83% for 1K LV models
87.5% for 1K G models
84% for 1.5K LV models
87.5% for 1.5K G models
86% for 2K LV models
90% fo r 2K G models
86% for 3K LV models
89% for 3K G models
Frequency regulation
Sync with line ±5% of nominal line frequency
(outside this range: ±0.5% of auto-selected nominal
frequency)
±0.5% of auto-selected
nominal frequency
Nominal output
[100V] [110V] [120V] [125V]
[200V] [208V] [220V] [230V] [240V] (G models)
Frequency
50 or 60 Hz, autosensing or configurable as a frequency converter
Output overload
Online mode:
102%~130% :12s
130%~150% :2s
>150% :shutdown after 300ms
Percent is based on nominal Watt/VA.
Transfer behavior can change (see output mode setting on page 14)
Battery mode:
102%~130% :12s
>130% :2s
Overload warning then transfer to stop output
Output overload
(Bypass mode)
102%~110% :Overload warning
110%~130% :shutdown after 5mins
130%~150% :shutdown after 15s
>150% :shutdown after 300ms
Percent is based on nominal current in bypass mode
Voltage waveform
Sinewave
Harmonic distortion
< 3% THDV on linear load
< 5% THDV on non-linear load
Transfer time
Online mode: 0ms
High Efficiency mode: 10ms maximum (due to loss of utility)
Power factor
Up to 0.9
Load crest ratio
Up to 3:1
Table 7. Electrical output connections
Model Output connection Output cable
9PX700RT 5-15R (4) No
9PX1000RT 5-15R (2)
9PX1500RT 5-15R (2)
9PX2000RT 5-20R(2) + L5-20R(1)
5-20R(2) Group1
5-20R(2) Group2
No
9PX3000RT 5-20R(2) + L5-30R(1)
5-20R(2) Group1
5-20R(2) Group2
No
9PX1000GRT (4) IEC10A
(2) IEC10A
(2) IEC10A (2) IEC 10A
No
9PX1500GRT
9PX2200GRT (4) IEC10A + (1) IEC16A
(2) IEC10A + (1) IEC16A group 1
(2) IEC10A group 2
(2) IEC 10A
9PX3000GRT
9PX3000GLRT L6-30R (1)
L6-20R (1) Group 1
L6-20R (1) Group 2
No