Tripp Lite MBP6K208 Eaton 9PX Maintenance Bypass for Select 5kVA to 6kVA 9PX UPS Systems, Hardwired Input/Output, 2 L6-30R Outlets, 3U Rack/Tower

Installation and user manual - Page 16

For MBP6K208. Also, The document are for others Tripp Lite models: 9PX 700 RT, 9PX 1000 RT, 9PX 1000GRT, 9PX 1500 RT, 9PX 1500GRT, 9PX 2000 RT, 9PX 2200 GRT, 9PX 3000 RT, 9PX 3000 GRT, 9PX 3000 GLRT, 9PX EBM 36V RT, 9PX EBM 48V RT, 9PX EBM 72V RT

PDF File Manual, 46 pages, Read Online | Download pdf file

Loading ...
Loading ...
Loading ...
Page 16
9PX 1-3 KVA US_EN
2. Presentation
Submenu Available settings Default settings
Com settings
Output signals [Relay] [DB9-1] [DB9-7] [DB9-8]
Sets events or fault that will actuate
Output signal parameters through
external contact connector or RS232
port
[Relay]: [On bat] [Low bat] [Bat fault]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
[DB9-1]: [On bat] [Low bat] [Bat fault]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
[DB9-7]: [On bat] [Low bat] [Bat fault]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
[DB9-8]: [On bat] [Low bat] [Bat fault]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
[Relay] [Bypass]
[DB9-1] [Low bat]
[DB9-7] [UPS OK]
[DB9-8] [On bat]
Remote command [Enabled] [Disabled]
If Enabled, shutdown or restart
commands from software are
authorized.
[Enabled]
Shutdown
commands
[Send CMD] [Output OFF] [OFF delay]
[restart]
Sets events or fault that will actuate
Output signal parameters through
external contact connector or RS232
port
[Send CMD]: [Yes] [No]
[Output OFF]: [No] [UPS] [Group 1]
[Group 2] [Group 1 + Group 2]
[OFF delay]: [0s] …[999s]
[Restart]: [Yes] [No]
Send CMD: [No]
Output OFF: [No]
OFF delay: [0s]
Restart: [Yes]
On battery notice
delay
[0s] ... [99s]
Sets delay before noticing on battery
information to software.
[0s]
General alarm [On battery] [Battery fault]
[Overload pre-alarm] [Internal fault]
[Ambient temp.] [Fan lock]
[Bypass overload] [Current limit]
[Short circuit] [Inverter overload]
[Power overload] [Low battery]
[On bypass] [UPS OK] [Load protected]
[Load powered] [Ext. charger ON]
Defines which event or fault generate
a general alarm through Output signal
screen.
[Internal fault]