Eaton Tripp Lite SmartOnline Series User Guide 614-40204—Rev 01 39
Table 15. Electrical Output (Continued)
All models Normal mode Battery mode
Power factor Up to 0.9
Load crest ratio Up to 3:1
* 200/208/220/230V are derated at 4600/4800/5100/5300W.
Table 16. Electrical Output Connections
Model Output connection Output cable
SU5000RT / SU6000RT
Hardwired
(2) L6-30R
(2) L6-20R
No
Table 17. Environmental and Safety
Certifications
IEC/EN 62040-1
IEC/EN 62040-2 :Cat. C2
IEC/EN 62040-3
UL1778 5th edition
CSA 22.2
EMC ( Emissions)*
CISPR32 (EN55032) Class A
AS/NZS CISPR32 Class A
IEC 61000 (-3-11)
IEC 61000 (-3-12)
FCC part 15 Class A
EMC (Immunity)
IEC 61000-2-2
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on signal ports)
IEC 61000-4-5, Level 4, Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
IEC 61000-4-12
* for output cable < 10m.
Agency markings* cTUVus/NOM(TUV NOM)/CE
Operating temperatures
0 to 40°C (32 to 104°F) in Online mode, with linear de rating for
altitude
Note: thermal protection switches load to bypass in case of
overheating.
Storage temperatures
0 to 40°C (32 to 104°F) with batteries
-25 to 55°C (-13 to 130°F) without batteries
Transit temperature
-25 to 55°C (-13 to 130°F)
Relative humidity 0 to 96% no condensing
Model Specifications
Loading ...
Loading ...
Loading ...