38 Eaton Tripp Lite SmartOnline Series User Guide 614-40204—Rev 01
Table 13. Electrical Input
Model Default input
(Voltage/Max Current)
Input nominal voltages Input voltage window at
rated load
SU5000RT 208V / 23.3A 200V, 208V, 220V, 230V, 240V 176-276V
SU6000RT 208V / 24.8A
Nominal frequency 50/60Hz auto-sensing
Frequency range
50Hz : 40-60Hz before transfer to battery
60Hz : 50-70Hz before transfer to battery
Bypass voltage range
-20% / +15% of nominal value (default)
Noise filtering MOV for normal and common mode noise
Table 14. Electrical Input Connections
Model Input connection
SU5000RT L6-30P cord or hardwired
SU6000RT
L6-30P cord or hardwired
Table 15. Electrical Output
All models Normal mode Battery mode
Voltage regulation ±1% ±1%
Efficiency
> 98% (High-Efficiency mode)
>93%
> 91%
Frequency regulation Sync with line ±5% of nominal line
frequency (outside this range: ±0.5% of
auto-selected nominal frequency)
±0.5% of auto-selected nominal
frequency
Nominal output
200*/208*/220*/230*/240V (voltage configurable)
5000 / 6000VA* 4500/5400W*
Frequency 50 or 60 Hz, auto-sensing or configurable as a frequency converter
Output overload
100-102% : no alarm
102-110% : load transfers to Bypass mode after 2 minutes
110-125% : load transfers to Bypass mode after 1 minute
125-150% : load transfers to Bypass mode after 10 seconds
> 150% : load transfers to Bypass mode after 500 ms
Output overload ( Bypass mode )
100-125% : no alarm
125-150% : UPS shuts down after one minute
> 150% : UPS shuts down after one second
Voltage waveform Sine wave
Harmonic distortion
< 2% THDV on linear load
< 5% THDV on non-linear load
Transfer time
Online mode: 0 ms (no break)
High-Efficiency mode: 10 ms maximum (due to loss of utility)
Model Specifications
Loading ...
Loading ...
Loading ...