Eaton Tripp Lite SmartOnline Series User Guide 614-40204—Rev 01 17
Table 7. User Settings (Continued)
Main Menu Screen Submenu Submenu Menu Function
FACTORY SETT FACTORY SETT? The factory sett command is
used to restore factory
settings.
LOCAL SETTINGS
LANGUAGE ENGLISH* (Default)
[FRANCAIS] [ESPANOL]
Sets displayed language for
all menus, status and alarms.
The UPS fault, event log data
and settings are in all
supported languages.
AUDIBLE ALARM
ENABLED* (Default)
[ENABLED] [DISABLED ON
BAT] [ALWAYS DISABLED]
Enables or disables the
audible alarm.
IN / OUT SETTINGS
OUTPUT VOLTAGE 120V* (LV Default) [100V]
[110V] [120V] [125V]
208V* (HV Default) [200V]
[208V] [220V] [230V] [240V]
Sets the UPS output voltage.
The UPS must be in standby
to choose output voltage
setting.
OUTPUT FREQUENCY AUTOSENSING* (Default)
[AUTO SENSING] [FREQ
CONV. 50HZ] [FREQ CONV.
60HZ]
Sets the output frequency, the
output frequency follows the
input frequency.
HIGH EFFIC. MODE DISABLED* (Default)
[ENABLED] [DISABLED]
Powers the UPS output from
bypass for High-Efficiency.
OVERLOAD PREALARM 102%* (Default) [50%]
[55%]....[100%][102%]
Sets the load % when
overload alarm occurs.
ON / OFF SETTINGS
COLD START ENABLED* (Default)
[ENABLED] [DISABLED]
Cold start allows the UPS to
start on battery power without
the presence of input mains
power.
AUTO RESTART ENABLED* (Default)
[ENABLED] [DISABLED]
Auto restart allows the UPS to
restart automatically when
input mains power recovers
after a complete battery
discharge.
AUTO START ENABLED* (Default)
[ENABLED] [DISABLED]
Enables the UPS to start as
soon as input mains power is
available, provided the input
mains power is within the
UPS operating specification.
START ON BYPASS ENABLED* (Default)
[ENABLED] [DISABLED]
Enables the UPS to start in
Bypass Mode if the input
mains power is available and
within specification.
SLEEP MODE ENABLED* (Default)
[ENABLED] [DISABLED]
If Disabled, LCD and
communication will turn off
immediately after the UPS is
OFF. If Enabled, LCD and
User Settings