CGa Series 3 Gas-Fired Water Boiler — Boiler Manual
11b
Troubleshooting — spark-pilot boilers (continued)
CHART 4 –– Spark-ignited pilot –– FLAME & POWER lights flashing
–– Usually indicates ame sensed when it shouldn’t be there ––
Electrical shock hazard — Wherever you see
TURN OFF POWER
, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
Are manual main shutoff valve and gas valve open ?
No Yes
Turn off power to boiler at service switch or breaker.
Wait at least 45 seconds.
Turn on power to boiler.
Restart boiler, following Operating instructions in this
manual (Section 9b) or on boiler label.
Look through the pilot inspection port to see if the pilot is
burning.
Is pilot burning?
No Yes
Leave main manual gas valve closed.
Turn off power to boiler at service switch or breaker.
Wait at least 45 seconds.
Turn on power to boiler.
Restart boiler, following Operating instructions in this
manual (Section 9b) or on boiler label.
Do FLAME and POWER lights still ash ?
No Yes
Replace gas valve.
Retest.
Are FLAME and POWER lights ashing?
No Yes
Replace control module.
Retest.
Allow boiler to continue cycling.
Are FLAME and POWER lights ashing?
No Yes
Replace control
module.
Retest.
Boiler may now be
operating
normally.
Perform start-up
procedures in
boiler manual to
verify proper
operation.
Replace control
module.
Retest.
Boiler should now
operate normally.
Original ashing
FLAME light
caused by gas
valve not
operating properly.
See normal
sequence of
operation,
Figure 24,
page 35.
▲ TURN OFF POWER ▲
to boiler at service switch or
breaker.
Open main manual gas
valve.
Turn on power to boiler at
service switch or
breaker.
Restart boiler per
operating instructions.
Perform start-up
procedures in boiler
manual to verify proper
operation.