50 | APPLICATION GUIDELINES
Single Zone Mega Wall Mounted Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
EQUIPMENT SELECTION PROCEDURE
Cooling / Heating Correction Factors
For the Single Zone Mega Wall Mounted system, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit.
Also, determine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity
correction factors as shown in Figures 17 through 20. Multiply the correction factors by the cooling or heating capacity obtained from the
capacity tables using design conditions. The resultant is the NET cooling or heating capacity.
Figure 17: LS090-240HEV1 Cooling Coefcient Factor.
Figure 18: LS090-240HEV1 Heating Coefcient Factor.
Cooling
9k,12k
18k,24k
49.2 65.6
To tal Pipe Length (ft)
100
24.6
90
Capacity(%)
Heating
24.6
100
95
9k,12k
18k,24k
49.2 65.6
To tal Pipe Length (ft)
Capacity(%)