Briggs & Stratton 040677 Standby Generator

User Manual - Page 27

For 040677.

PDF File Manual, 140 pages, Read Online | Download pdf file

Loading ...
Loading ...
Loading ...
Part No. 80106286
Revision C
27
Installation
Final Installation Considerations
Final Installation Considerations
Engine Oil
Any attempt to crank or start the
engine before it has been correctly filled with the
recommended oil will result in equipment failure and
service codes.
Refer to Maintenance in the Operation section for oil fill
information.
Damage to equipment resulting from failure to obey this
instruction will void the engine and generator warranty.
This engine ships from the factory pre-run and filled with
full synthetic oil (API SJ/CF 5W-30). This step allows for
system operation in a wide range of temperature and
climate conditions. Before starting the engine, check the
oil level as described in the Maintenance section.
Using full synthetic oil does not alter the required oil
change intervals as described in the Operation section.
Battery
WARNING
Storage batteries give o
explosive hydrogen gas during recharging. The
slightest spark could ignite hydrogen and cause an
explosion, resulting in death or serious injury.
DO NOT dispose of the battery in a fire. Recycle the
battery.
DO NOT allow any open flame, spark, heat, or
lit cigarette in the area of the battery during the
battery-charging process and for several minutes
after charging.
WARNING
Generator voltage could
cause electrical shock or burns, resulting in death or
serious injury.
A licensed professional must perform the
installation.
Disconnect all sources of electricity before
installing or servicing equipment.
Ground the system before applying power.
WARNING
Battery electrolyte
fluid contains acid and is extremely caustic. Contact
with battery contents could cause severe chemical
burns.
DO NOT open or mutilate the battery.
Wear protective goggles, a rubber apron, rubber
boots, and rubber gloves.
Immediately wash electrolyte from skin with water.
If electrolyte contacts the eyes, immediately flush
them with water and seek medical attention.
Wash down spilled electrolyte with an acid-
neutralizing agent.
The installer must supply and install a rechargeable 12V
starting battery. The starting battery MUST conform to
the specifications shown in the following chart.
BATTERY SPECIFICATIONS
Specifications Standard Cold Start (Less
than 30° F / -1° C)
Volts 12VDC 12VDC
Amps (Minimum) 540 CCA (Cold
Cranking Amps)
800 CCA(Cold
Cranking Amps)
Construction Wet Lead Acid Wet Lead Acid
Terminal Type Top Post Type
Battery
Top Post Type
Battery
Dimensions
(Maximum)
BCI Size 26 or
BCI Size 51
BCI Size 24
WARNING
With the battery connected,
the generator may crank and start without warning,
resulting in death or serious injury.
Do not connect the negative (-) cable at the battery
until the installation is complete.
Install the battery as described in Servicing the Battery in
the Maintenance section of this manual. Always connect
the negative cable last and secure the red positive
terminal insulator.
Use the supplied tie-down strap to secure the battery to
the unit. Attach each end of the strap to the existing tabs
in the base of the unit.