Installation
Anchoring and Wind Rating
Cold Weather Kit
If the generator operates in temperatures below 30° F
(-1° C), Briggs & Stratton highly recommends that the
installer install a cold weather kit.
Oil Sump Warmer Kit, Part Number 6840-00, includes:
Oil sump warmer
Install brackets
Hardware
Harness
Fuel Regulator Warmer Kit, Part Number 6845-00,
includes:
Regulator warmer
Deflector bracket
Harness
Battery Warmer Kit, Part Number 6869-00, includes:
Battery warmer
Harness
Find these items at the local service dealer.
For more information, please call800-732-2989between
8:00 a.m. and 5:00 p.m. CT.
Figure 5
Anchoring and Wind Rating
Concrete Anchoring of Unit to Poured
or Existing Slab
To achieve the listed wind rating, the generator must be
installed in strict compliance with this Installation and
Operation Manual. The product components must be of
the material specified and all screws must be installed
in accordance with the applicable provisions and the
anchor manufacturers published installation instructions.
The concrete slab or pad must meet the requirements
below and the generator must be anchored with one of
the following anchor types.
Anchor Types
1. Quantity (4) 3/8-inch dia. ITW Red Head Large
Diameter Tapcon (LTD) with 1-1/2-inch embedment,
2-inch min. edge of concrete, and 6-inch min. spacing
from neighboring concrete anchors typ. If anchor
does not provide a .812-inch min. OD integrated
washer out-of-box, employ (1) .812-inch min. OD
washer per anchor.
2. Quantity (4) 3/8-inch dia. DeWalt Screw-Bolt+ with
1-1/2-inch embedment, 4-inch min. edge of concrete,
and 6-inch min. spacing from neighboring concrete
anchors typ. If anchor does not provide a .812-inch
min. OD integrated washer out-of-box, employ (1)
.812-inch min. OD washer per anchor.
3. Quantity (4) 3/8-inch-16 SAE Gr. 2 min. or SS bolt
with .812-inch min. OD washer, typ. Ensure 1/2-inch
min. thread engagement U.N.O. by bolt and/or insert
manufacturer, typ.
There are four 7/16-inch hole locations (A) in the base of
the generator in which to anchor the unit.
40.6 in
(1030 mm)
20.9 in
(530 mm)
A
A
Figure 6
Concrete Slab/Pad Types
WIND
RATING
MPH
ANCHOR
TYPE
PAD
MODEL
PAD DIMENSIONS
CONCRETE
SPEC
WIDTH LENGTH THICKNESS
Up to 186
(at grade)
3 Pre-cast
(contact
dealer)
37 in
(940 mm)
55 in
(1397 mm)
4 in
(102 mm)
3000 psi
(20.70 MPa)
Up to 186
(at grade)
1 or 2 Poured 37 in
(940 mm)
55 in
(1397 mm)
4 in
(102 mm)
3000 psi
(20.70 MPa)
Find these items at the local service dealer.
Unless mandated by local or state
codes, or required to achieve wind rating, a concrete slab
or pad is not required.
Not for
Reproduction