WDV Series Gas Fireplace
ing to the difference between the Set temperature and
the Room temperature. There is no manual ame height
adjustment. The fan speed will also automatically adjust
if turned on.
there will a 10 second delay for the ame adjust-
ment when the replace is turned on.
1. When Set Temp. is 3° F or higher than Room Temp.,
ame height will be on High.
2. When Set Temp. is 2° F higher than Room Temp.,
ame height will be on Medium.
3. When Set Temp. is 1° F higher than Room Temp.,
ame height will be on Low.
4. When Set Temp. is equal to Room Temp., ame height
does not change (stays on low).
5. When Set Temp. is lower than Room Temp., the re-
place will be shut off.
6. When Set Temp. is 1° F higher than Room Temp.,
again the ame height will be on Low.
7. the fan speed follows the ame height, if the fan is
turned on.
To exit Smart Mode
®
thermostat and shut off the re-
place;
a. push and hold the THERMO buttons for 3 sec-
onds, Or
b. press the OFF button, Or
c. slide down on the arrow buttons.
To shut off the Smart Mode
®
thermostat option and return
to regular thermostat mode, press and hold the THERMO
button and the ON/UP button at the same time for 3 sec-
onds again.
Figure 50
Blower will only work with
ame on.
The blower speed control function
is used to adjust the speed of the
blower connected to the Signature
Command System. There are four
speed levels, Off, Low, Medium,
High.
1. Press the FAN button to enter
the blower speed control mode.
The fan icon will start ashing.
2. Press the ON/up and OFF/down button to increase/de-
crease the blower speed.
3. Press the fan button again to conrm the speed set-
ting. If the replace is on, the blower speed will take
effect right away; if the replace is off, the receiver will
remember this setting and the blower is still off (see
blower On Delay and Off Delay in the next section).
4. After the signal is sent, the ON/up and OFF/down but-
tons become ame height controller again.
5. When the fan button is ashing, slide up and down on
the arrow buttons will turn the blower speed to High
or Off directly without pressing the fan button again to
conrm.
6. If the blower is turned on using the FAN button, the
blower speed will adjust automatically when using
Smart Mode
®
thermostat (See Smart Mode
®
thermo-
stat section).
Figure 51
1. Hold the FAN button for 3 sec-
onds until two numbers ap-
pear on the LCD screen. The
left number is blower On Delay
and the right number is blower
Off Delay Time.
2. When the rst number is ash-
ing, use the ON/up button to
set the desired On Delay Time
from 0 to 15 min.
3. Press the OFF/down button to
jump to the Off Delay Time setup.
4. When the second number is ashing, use the ON/up
button again to set the desired Off Delay Time from 0
to 15 min.
5. Press the OFF/down button again to nish the setup
and the new settings will be transmitted to the receiv-
er.
6. The default settings are 5 minutes for the On Delay
Time and 8 minutes for the Off Delay Time, as shown.
Figure 52
The light brightness control func-
tion is used to adjust the bright-
ness of the light bulbs connected
to the AC module on the Signa-
ture Command System. There
are four light brightness levels
dened: Off, Low, Medium, High
1. Press the LIGHT button to en-
ter the light brightness control
mode. The LIGHT icon will
start ashing.
2. Press the On/up and OFF/
down buttons to increase/de-
crease the light brightness (Off-Low-Medium-High).
3. Press the light button again to conrm the setting. The
new setting will be transmitted to the receiver.
4. After the signal is sent, the On/up and Off/down but-
Figure 52
Figure 51
Figure 50