WDV Series Gas Fireplace


There are two basic types of direct-vent installation:
Horizontal Termination
Vertical Termination
It is important to select the proper length of vent pipe for
the type of termination you choose. It is also important to
note the wall thickness.

Select the amount of vertical rise desired. All horizontal run
of venting must have 1/4" rise for every 12" of run towards
the termination below 7Z\x feet of vertical rise from the oor
of the replace. With 7Z\x feet or more vertical rise from
the oor of the replace, the horizontal run may run level.
NEVER run vent piping down.
You may use up to three 90° elbows in this vent congura-
tion. Refer to Vertical/Horizontal Termination Congurations
on Page 15.
Horizontal venting which incorporates the twist lock pipe
must be installed on a level plane without an inclining or
declining slope.

Measure the distance from the replace oor to the ceil-
ing. Add the ceiling thickness, the vertical rise in an attic
or second story, and allow for sufcient vent height above
the roof line.
 You may use two 45° elbows in place of a 9elbow.
You must follow rise to run ratios when using 45° elbows.
The appliance is approved for use with three 90° elbows
maximum or a combination of 90° and 45° elbows up to
a maximum of 270°.






  

  
       
     
     
      






    

     
   
        
      



For two-story applications, restops are required at each
oor level. If an offset is needed in the attic, additional pipe
and elbows will be required.
You may use a chase with a vent termination with exposed
pipe on the exterior of the house.
Refer to Installing A Vent System in an Outside Chase
below. If pipe is enclosed in chase, it is not exposed.
It is very important that the venting system maintain its bal-
ance between the combustion air intake and the ue gas
exhaust. Certain limitations apply to vent congurations
and must be strictly followed.


A chase is a vertical boxlike structure built to enclose
venting that runs along the outside of a building. A chase
is required for such venting.