Address DIP switch: Static pressure DIP switch:
Dial code selecon Website address
Address dialing S1+S2: When the user uses the
centralized controller, the address dialing is
required.
Network address: The address silkscreen is NET
address, which is composed of a 16-bit address
rotary code S2 plus a two-digit DIP switch S1
[Set during engineering installaon, no network
funcon does not need to be set]
When S2 is 00 (the dialing code is not connected),
the network address value is the value of S2;
When S2 is 10 (corresponding to the switch of the
hardware connected to the 10K resistor), the
network address value is S2 plus 32;
When S2 is 01 (corresponding to the dial code of
the 5.1K resistor connected to the hardware is
turned on), the network address value is the
value of S2 plus 16;
When S2 is 11 (all dialing codes are on), the
network address value is the value of S2 plus 48.
Determined by dial code S2 1-10K 2-5.1K
S2 + 48
S2 + 32
S2 + 16
S2
SW4
This dialing code is only valid for 1-3. Composion
of binary code, respecvely corresponding to
different wind profile stac pressure.
000 is the default; 000/001/010/011/100/101/110/
111, with different capacies of indoor unit and
electric heang and PSC for selecon and use,
corresponding to different air volumes, see air
volume table for details.