Cooper&Hunter CH-60AHU Air Conditioner

User Manual - Page 37

For CH-60AHU.

PDF File Manual, 53 pages, Read Online | Download pdf file

CH-60AHU photo
Loading ...
Loading ...
Loading ...
Wiring
BEFORE PERFORMING ANY
ELECTRICAL WORK, READ
THESE REGULATIONS
1. All wiring must comply with local and naonal
electrical switchs, regulaons and must be
installed by a licensed electrician.
2. All electrical connecons must be made
according to the Electrical Connecon Diagram
located on the panels of the indoor and outdoor
units.
3. If there is a serious safety issue with the power
supply, stop work immediately. Explain your
reasoning to the client, and refuse to install the
unit unl the safety issue is properly resolved.
4. Power voltage should be within 90-110% of
rated voltage. Insufficient power supply can
cause malfuncon, electrical shock, or fire.
5. If connecng power to fixed wiring, a surge
protector and main power switch should be
installed.
6. If connecng power to fixed wiring, a switch
or circuit breaker that disconnects all poles and
has a contact separaon of at least 1/8in (3mm)
must be incorporated in the fixed wiring. The
qualified technician must use an approved
circuit breaker or switch.
Do not let wires touch or rest against refrigerant
tubing, the compressor, or any moving parts
within the unit.
If the unit has an auxiliary electric heater, it must
be installed at least 1 meter (40in) away from
any combusble materials.
To avoid geng an electric shock, never touch
the electrical components soon aer the power
7. Only connect the unit to an individual branch
circuit outlet. Do not connect another
appliance to that outlet.
8.
Make sure to properly ground the air condioner.
9. Every wire must be firmly connected. Loose
wiring can cause the terminal to overheat,
resulng in product malfuncon and possible fire.
10.
11.
12.
13.
Make sure that you do not cross your
electrical wiring with your signal wiring.
This may cause distoron and
interference.
14.
The unit must be connected to the
main outlet. Normally, the power supply
must have a impedance of 32 ohms.
15.
No other equipment should be
connected to the same power circuit.
16.
Connect the outdoor wires before
connecng the indoor wires.
supply has been turned off. Aer turning off
the power, always wait 10 minutes or more
before you touch the electrical components.
WARNING
BEFORE PERFORMING ANY
ELECTRICAL OR WIRING WORK,
TURN OFF THE MAIN POWER TO
THE SYSTEM.
NOTE ON AIR SWITCH
When the maximum current of the air
condioner is more than 16A, an air switch
or leakage protecon switch with
protecve device shall be used(purchased
seperately) . When the maximum current
of the air condioner is less than 16A, the
power cord of air condioner shall be
equipped with plug (purchased seperately) .
Wiring
Page 37
Loading ...
Loading ...
Loading ...