66 | PRODUCT DATA
Single Zone Vertical Air Handling Unit Engineering Manual
Outdoor Air
Temp.
Indoor Air Temp.: °FDB
61.0 64.0 68.0 70.0 72.0 75.0
°F DB °F WB TC PI TC PI TC PI TC PI TC PI TC PI
-4 -4.4 27.83 4.71 27.21 4.86 26.43 5.02 26.00 5.10 25.65 5.17 24.72 5.33
0 -0.4 31.64 4.77 30.93 4.92 30.05 5.08 29.56 5.17 29.16 5.24 28.10 5.40
5 4.5 36.39 4.84 35.58 5.00 34.56 5.16 34.00 5.25 33.55 5.32 32.33 5.48
10 9 39.15 4.92 38.27 5.08 37.18 5.25 36.57 5.34 36.09 5.41 34.77 5.57
17 15 43.58 4.99 42.06 5.15 40.74 5.31 40.00 5.40 39.41 5.47 37.89 5.63
20 19 45.68 5.00 44.23 5.15 42.75 5.33 41.96 5.43 41.32 5.51 39.75 5.66
25 23 49.21 5.02 47.75 5.17 46.09 5.37 45.22 5.47 44.52 5.56 42.84 5.71
30 28 52.77 5.07 51.14 5.24 49.38 5.40 48.47 5.52 47.75 5.62 45.99 5.76
35 32 56.33 5.12 54.54 5.30 52.68 5.44 51.73 5.57 50.98 5.67 49.13 5.81
40 36 59.20 5.27 57.54 5.45 55.70 5.61 54.74 5.73 53.97 5.82 52.01 5.97
45 41 62.79 5.46 61.29 5.64 59.48 5.82 58.50 5.92 57.71 6.01 55.61 6.18
47 43 64.23 5.53 62.79 5.72 61.00 5.90 60.00 6.00 59.20 6.08 57.05 6.26
50 46 64.41 5.50 63.12 5.66 61.55 5.83 60.66 5.91 59.95 5.98 57.92 6.15
55 51 64.73 5.44 63.66 5.57 62.48 5.71 61.76 5.77 61.19 5.82 59.38 5.95
60 56 65.04 5.38 64.20 5.49 63.41 5.59 62.86 5.63 62.43 5.66 60.83 5.75
63 59 65.23 5.35 64.52 5.43 63.96 5.51 63.53 5.54 63.18 5.56 61.71 5.63
68 64 65.42 5.31 64.85 5.38 64.52 5.44 64.19 5.46 63.93 5.47 62.59 5.51
Table 40: Maximum Heating Capacity Table for LUU488HV + LVN480HV.
Maximum Heating Capacity Table for LV480HV (LUU488HV + LVN480HV)
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total
Capacity (kBtu/h)
PI: Power Input (kW) (includes compressor, indoor fan motor, and outdoor fan
motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Direct interpolation is permissible.
Do not extrapolate.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF
dry bulb (DB) and 60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF
dry bulb (DB) and 43ºF wet bulb (WB).