Loading ...
Loading ...
Loading ...
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
PRODUCT DATA | 59
Product Data
Table 33: Heating Capacity Table for LUU368HV + LVN360HV4.
Heating Capacity Table for LV360HV4 (LUU368HV + LVN360HV4)
Outdoor Air
Temp.
Indoor Air Temp.: °FDB
61.0 64.0 68.0 70.0 72.0 75.0
°F DB °F WB TC PI TC PI TC PI TC PI TC PI TC PI
-4 -4.4 16.28 2.30 15.09 2.39 15.00 2.41 14.82 2.43 14.68 2.44 14.02 2.53
0 -0.4 19.29 2.35 18.16 2.44 17.87 2.47 17.61 2.50 17.41 2.51 16.67 2.60
5 4.5 22.86 2.41 21.80 2.50 21.28 2.55 20.93 2.58 20.66 2.60 19.82 2.69
10 9 25.26 2.47 24.24 2.55 23.56 2.62 23.16 2.65 22.83 2.68 21.93 2.76
17 15 27.89 2.54 26.92 2.62 26.07 2.70 25.60 2.75 25.22 2.79 24.25 2.87
20 19 29.49 2.59 28.55 2.67 27.59 2.76 27.08 2.82 26.67 2.86 25.66 2.94
25 23 32.16 2.69 31.21 2.76 30.12 2.87 29.55 2.93 29.10 2.97 28.00 3.05
30 28 34.86 2.79 33.78 2.88 32.62 2.97 32.02 3.04 31.54 3.09 30.38 3.17
35 32 37.55 2.89 36.36 3.00 35.12 3.07 34.49 3.15 33.98 3.20 32.76 3.28
40 36 39.47 2.98 38.36 3.08 37.14 3.17 36.49 3.23 35.98 3.29 34.68 3.37
45 41 41.86 3.08 40.86 3.19 39.66 3.29 39.00 3.35 38.47 3.39 37.07 3.49
47 43 42.82 3.13 41.86 3.23 40.66 3.33 40.00 3.39 39.47 3.44 38.03 3.54
50 46 42.94 3.11 42.08 3.20 41.04 3.29 40.44 3.34 39.97 3.38 38.62 3.47
55 51 43.15 3.07 42.44 3.15 41.65 3.22 41.18 3.26 40.79 3.29 39.59 3.36
60 56 43.36 3.04 42.80 3.10 42.27 3.16 41.91 3.18 41.62 3.20 40.56 3.25
63 59 43.49 3.02 43.01 3.07 42.64 3.12 42.35 3.13 42.12 3.14 41.14 3.18
68 64 43.61 3.00 43.23 3.04 43.02 3.08 42.80 3.08 42.62 3.09 41.73 3.12
PERFORMANCE DATA
Heating Capacity Tables
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC:
Total Capacity (kBtu/h)
PI: Power Input (kW) (includes compressor, indoor fan motor, and
outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Direct interpolation is permissible.
Do not extrapolate.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refriger-
ant piping.
0 ft. level difference between outdoor and indoor units.
Nominal heating capacity rating obtained with air entering the indoor
unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB), and outdoor ambi-
ent conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Loading ...