Loading ...
Loading ...
Loading ...
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
12 | PRODUCT DATA
Single Zone Vertical Air Handling Unit Engineering Manual
Table 3: Vertical Air Handling Unit General Data, continued.
Type Vertical Air Handling Unit
System (Model) (Indoor Unit / Outdoor
Unit)
LV180HV4
(LVN180HV4/
LUU188HV)
LV240HV4
(LVN240HV4/
LUU248HV)
LV360HV4
(LVN360HV4/
LUU368HV)
LV420HV
(LVN420HV/
LUU428HV)
LV480HV
(LVN480HV/
LUU488HV)
Unit Data
Refrigerant Type
3
R410A
Additional Refrigerant Charge (oz./ft.) 0.43
Refrigerant Control EEV
Indoor Unit Sound Pressure Level (dB(A))
(H/M/L)
4
42 / 42 / 41 43 / 42 / 41 45 / 44 / 43 48 / 45 / 44 49 / 48 / 44
Outdoor Unit Sound Pressure Level
(dB(A)) (Cool/Heat)
4
48 / 52 48 / 52 52 / 54 52 / 54 52 / 54
Indoor Unit Net / Shipping Weight (lbs.) 129 / 140 129 / 140 165 / 188 165 / 188 165 / 188
Outdoor Unit Net / Shipping Weight (lbs.) 129 / 141 129 / 141 203 / 232 203 / 232 203 / 232
Power Wiring / Communications Cable
(No. x AWG)
2
4 x 18
Power Supply (No. x AWG) 3 x 12 3 x 12 3 x 10 3 x 10 3 x 10
Compressor (Type x Qty.) Twin Rotary x 1
Dehumidication Rate (pts./hr.) 2 2.5 3.4 4.3 5.2
Fan
Indoor Unit Type x Qty. Sirocco x 1
Outdoor Unit Type x Qty. Propeller x 1 Propeller x 1 Propeller x 2 Propeller x 2 Propeller x 2
Motor / Drive Brushless Digitally Controller / Direct
Airflow Rate
Indoor Unit (H / M / L [CFM]) 640 / 580 / 480 710 / 640 / 480 1,100 / 1,000 / 900 1,260 / 1,100 / 1,000 1,400 / 1,260 /
1,000
Outdoor Unit (CFM) 2,048 2,048 1,942 x 2 1,942 x 2 1,942 x 2
Factory Set (High) External Static Pressure
(in.wg)
0.3
Piping
Liquid (in.) 3/8
Vapor (in.) 5/8
Indoor Unit Condensate Drain I.D. (in.) Primary & Secondary: 3/4 FPT
Minimum / Maximum Pipe Length (ft.)
5
6.6 / 164 6.6 / 164 6.6 / 246 6.6 / 246 6.6 / 246
Piping Length (no additional refrigerant, ft.) 24.6
Maximum Elevation Difference (ft.) 98.4
EEV: Electronic Expansion Valve, IDU: Indoor Unit, ODU: Outdoor Unit. This unit comes with a
dry helium charge.
This data is rated 0 ft above sea level, with 24.6 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB); and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF
wet bulb (WB); and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1
Power Input is rated at high speed.
2 All communication / connection (power) cable from the outdoor unit to the indoor unit
are field supplied and is to be a minimum four-conductor, 18 AWG, stranded, shielded or
unshielded (if shielded, it must be grounded to the chassis of ODU only), and must comply
with applicable local and national codes.
3 Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under
section 608 of CAA.
4 Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and
are the same in both cooling and heating mode. These values can increase due to ambient
conditions during operation.
5 Piping lengths are equivalent.
GENERAL DATA / SPECIFICATIONS
Loading ...
Loading ...
Loading ...