52 | PRODUCT DATA
Single Zone Vertical Air Handling Unit Engineering Manual
Table 26: Cooling Capacity Table for LUU188HV + LVN180HV4.
Cooling Capacity Table for LV180HV4 (LUU188HV + LVN180HV4)
PERFORMANCE DATA
Cooling Capacity Tables
Outdoor
Air
Temp.
(°F DB)
Indoor Air Temp. °F DB / °F WB
68 / 57 72 / 61 77 / 64 80 / 67 86 / 72 90 / 75
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
-4 17.70 12.85 0.80 18.80 13.58 0.83 19.89 13.14 0.86 20.69 13.42 0.87 22.09 13.53 0.88 23.19 13.79 0.90
0 17.69 12.93 0.81 18.79 13.66 0.84 19.88 13.22 0.87 20.68 13.50 0.88 22.08 13.61 0.89 23.18 13.87 0.91
5 17.67 13.04 0.82 18.77 13.77 0.85 19.87 13.34 0.88 20.66 13.62 0.89 22.06 13.73 0.91 23.16 13.99 0.93
10 17.66 13.14 0.83 18.76 13.88 0.86 19.85 13.44 0.89 20.64 13.73 0.90 22.05 13.84 0.92 23.14 14.10 0.94
15 17.65 13.25 0.84 18.74 13.99 0.88 19.84 13.55 0.91 20.63 13.83 0.92 22.03 13.95 0.94 23.12 14.22 0.95
20 17.63 13.35 0.86 18.73 14.10 0.89 19.82 13.65 0.92 20.61 13.94 0.93 22.01 14.06 0.95 23.11 14.33 0.97
25 17.62 13.45 0.87 18.71 14.21 0.90 19.81 13.76 0.93 20.60 14.05 0.94 22.00 14.17 0.96 23.09 14.44 0.98
30 17.60 13.56 0.88 18.70 14.32 0.91 19.79 13.87 0.95 20.58 14.16 0.96 21.98 14.28 0.98 23.07 14.55 1.00
35 17.59 13.66 0.89 18.68 14.43 0.93 19.78 13.97 0.96 20.57 14.27 0.97 21.96 14.39 0.99 23.05 14.66 1.01
40 17.58 13.76 0.91 18.67 14.54 0.94 19.76 14.08 0.97 20.55 14.37 0.98 21.94 14.49 1.00 23.04 14.77 1.02
45 17.56 13.87 0.92 18.66 14.65 0.95 19.75 14.18 0.99 20.53 14.48 1.00 21.93 14.60 1.02 23.02 14.88 1.04
50 17.55 13.97 0.93 18.64 14.75 0.96 19.73 14.29 1.00 20.52 14.59 1.01 21.91 14.71 1.03 23.00 14.99 1.05
55 17.54 14.07 0.94 18.63 14.86 0.98 19.72 14.39 1.01 20.50 14.69 1.02 21.89 14.82 1.04 22.98 15.10 1.06
60 17.52 14.17 0.95 18.61 14.97 0.99 19.70 14.50 1.03 20.49 14.80 1.04 21.88 14.93 1.06 22.97 15.21 1.08
65 17.51 14.27 0.97 18.60 15.08 1.00 19.69 14.60 1.04 20.47 14.91 1.05 21.86 15.03 1.07 22.95 15.32 1.09
70 17.50 14.38 0.98 18.58 15.19 1.01 19.67 14.70 1.05 20.46 15.01 1.06 21.84 15.14 1.08 22.93 15.43 1.10
75 17.08 14.14 1.03 18.16 14.96 1.07 19.24 14.50 1.11 20.03 14.81 1.12 21.41 14.96 1.14 22.50 15.25 1.16
80 16.66 13.90 1.08 17.74 14.72 1.12 18.82 14.29 1.16 19.60 14.61 1.18 20.98 14.77 1.20 22.06 15.07 1.22
85 16.24 13.64 1.14 17.32 14.47 1.18 18.40 14.06 1.22 19.17 14.39 1.24 20.55 14.57 1.26 21.63 14.88 1.28
90 15.82 13.39 1.19 16.90 14.22 1.23 17.97 13.84 1.28 18.75 14.17 1.29 20.12 14.36 1.32 21.20 14.69 1.34
95 15.37 13.25 1.24 16.44 14.09 1.29 17.51 13.73 1.33 18.00 13.86 1.35 19.65 14.29 1.38 20.72 14.62 1.40
100 14.99 12.89 1.30 16.06 13.74 1.34 17.13 13.40 1.39 17.77 13.65 1.41 19.28 13.98 1.43 20.35 14.32 1.46
105 14.62 12.54 1.35 15.69 13.38 1.40 16.76 13.08 1.45 17.53 13.43 1.46 18.90 13.67 1.49 19.97 14.02 1.52
110 14.24 12.11 1.40 15.32 12.95 1.45 16.39 12.67 1.50 17.16 13.03 1.52 18.53 13.29 1.55 19.60 13.64 1.58
115 13.87 11.75 1.45 14.94 12.58 1.51 16.01 12.34 1.56 16.79 12.70 1.58 18.15 12.97 1.61 19.22 13.33 1.64
118 13.65 11.66 1.49 14.72 12.51 1.54 15.79 12.27 1.60 16.56 12.64 1.61 17.93 12.92 1.64 19.00 13.29 1.68
122 13.57 11.63 1.53 14.64 12.48 1.58 15.71 12.25 1.64 16.49 12.62 1.66 17.85 12.91 1.69 18.92 13.28 1.72
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity
(kBtu/h)
SHC: Sensible Capacity (kBtu/h) PI: Power Input (kW) (includes compressor, indoor fan
motor and outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Cooling operating range with the Low Ambient Baffle Kit (sold separately) is -4°F to
+122°F.
3. Grey shading indicates reference data. When operating the unit at this temperature,
these values can be different by discontinuous operation.
4. Direct interpolation is permissible.
Do not extrapolate.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb
(DB) and 67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and
75ºF wet bulb (WB).