Loading ...
Loading ...
Loading ...
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
PRODUCT DATA | 45
Product Data
Table 17: Air Filter Static Pressure Drop Factors.
If the air filter has been installed, the ESP value has to be set.
For every increase in static pressure by 0.01 in. wg, the ESP value must be increased
by 1.
Air Filter Static Pressure Drop Factors
Capacity (kBtu/h [tons]) Flow Rate (CFM) Static Pressure Drop (in wg)
18 (1.5) High (640) -0.04
Middle(580) -0.04
Low (480) -0.04
24 (2.0) High (710) -0.04
Middle(640) -0.04
Low (480) -0.04
36 (3.0) High (1100) -0.08
Middle(1000) -0.08
Low (900) -0.08
42 (3.5) High (1260) -0.09
Middle(1100) -0.08
Low (1000) -0.08
48 (4.0) High (1400) -0.09
Middle(1260) -0.09
Low (1000) -0.08
Do not operate with less than the minimum airow. If an airow is used
below the minimum, there is a risk of damage to the product.
Airflow rates in the table above are listed in CFM.
Do not operate with less than the minimum airow. If an air-
ow is used below the minimum, there is a risk of re, which may
lead to physical injury or death.
Table 18: Minimum Airow by Heater Capacity.
Capacity (kBtu/h [tons]) Heater Capacity (kW)
3, 5 8, 10 15 20
18 (1.5) 480 480 Not available Not available
24 (2.0) 480 480 Not available Not available
36 (3.0) 900 900 900 900
42 (3.5) 1000 1000 1000 1000
48 (4.0) 1000 1000 1000 1000
Minimum Airflow by Heater Capacity