Richmond RMTGHRH111DVLN Encore 11 GPM 199,900 BTU Tankless Natural Gas Water Heater

User Manual - Page 68

For RMTGHRH111DVLN.

PDF File Manual, 86 pages, Read Online | Download pdf file

RMTGHRH111DVLN photo
Loading ...
Loading ...
Loading ...
AP18733 REV. 3.2.17
68
Error Code Error Code Description Possible Remedies
Er:16
Operating Temperature Sen-
sor or DHW Sensor detects
Water Temperature Greater
than 199°F (93°C)
This Error Code will go away when the DHW temperature decreases.
If Error happens again:
1. Check if dip switch High Fire setting is ON. Switches 6 and 7 should be OFF for normal
operation.
2. Check if DHW pipe is blocked. Ensure there is enough water owing to the water heater.
3. Check DHW sensor at DHW outlet. If resistance is zero, replace the sensor.
4. Check Operating Temperature sensor at the heat exchanger. If resistance is zero, replace
the sensor.
5. If the problem persists, replace the main control.
Er:20
High Limit Overheat Switch
– Closed is Normal, Open is
Fault
Press the Power button to clear the Error Code.
1. Inspect the High Limit Overheat switch. Ensure proper connections.
2. Check High Limit Overheat switch resistance. If resistance is zero, replace the switch.
3. If the problem persists, replace the main control.
Er:29
APS/Condensate – Closed
is Normal, Open is Fault
(Condensate Drain Trap)
Press the Power button to clear the Error Code.
1. Check APS/Condensate and main controller connections. Ensure all are secure.
2. Check APS/Condensate resistance. If resistance is zero, replace the switch.
3. Check APS/Condensate hose. Ensure it is connected and in good condition.
4. Check condensate line and termination for blockages.
5. Check exhaust vent for blockages.
6. If the problem persists, replace the main control.
Er:31
Water Inlet Sensor Open or
Short
This Error Code will go away when inlet water temperature decreases.
If Error happens again:
1. Check inlet water temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
Er:32
Water Outlet Sensor Open or
Short
This Error Code will go away when outlet water temperature decreases.
If Error happens again:
1. Check DHW outlet temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
Er:33
H/X Temperature Sensor
Open or Short
This Error Code will go away when outlet water temperature decreases.
If Error happens again:
1. Check operating temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
Er:35
Exhaust Sensor Open or
Short
This Error Code will go away when exhaust temperature decreases.
If Error happens again:
1. Check exhaust temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. Check exhaust vent for blockage.
4. If the problem persists, replace the main control.
Er:39
Flame Detected after Exiting
a Flame On Condition
This Error Code will go away when the false ame condition is remedied.
If Error happens again:
1. Check the water heater cover. Ensure it is secure. Flame detection sensor can detect an external
light source.
2. Check ame detection sensor. Ensure connections are secure. Normal operating settings are more
than 2.5DC before ignition, less than 2.5DC after ignition.
3. If the problem persists, replace the main control.
Er:40
Gas Leakage continuously
detected for 10 Minutes, or
three times within One Hour
(Greater than 5 Seconds
Each Time)
IMPORTANT: If you smell gas, STOP! Follow the instructions on page 2, this manual, and call a quali-
ed service technician or the fuel gas utility.
Press the Power button to clear the Error Code.
If Error happens again:
1. Check the water heater cover. Ensure it is secure.
2. Check gas connections for leakage with a soapy solution. Fix any leaks.
3. Check condition of the burner assembly.
4. If the problem persists, replace the main control.