Purging the unit
From factory the unit is supplied and set with a pre-charge of nitrogen gas. (insert gas) Therefore, all insert gas must be purged
before connecting the assembly piping.
Unscrew the pinch pipe at the end of each refrigerant pipe.
RESULT : All inert gas escapes from the indoor unit.
• Topreventdirtorforeignobjectsfromgettingintothepipesduring
installation, do NOT remove the pinch pipe completely until you are
ready to connect the piping.
• Connecttheindoorandoutdoorunitsusingpipeswithared
connections(not supplied). For the lines, use insulated, unwelded,
degreased and deoxidized copper pipe (Cu DHP type to ISO 1337 or
UNI EN 12735-1), suitable for operating pressures of at least 4200kPa
and for a burst pressure of at least 20700kPa. Copper pipe for hydro-
sanitary applications is completely unsuitable.
• Forsizingandlimits(heightdierence,linelength,max.bends,
refrigerant charge, etc.) see the outdoor unit installation manual.
•Allrefrigerantconnectionmustbeaccessible,inordertopermiteither
unit maintenance or removing it completely.
The designs and shape are subject
to change according to the model.