Advanced Settings
Heating & Cooling
u To access the Heating and Cooling, click Advanced Settings, and enter the Professional Access Code
u Click on a setting and use the scroll wheel to modify the default value. From this menu you can adjust:
TITLE Default Max Min Description
Fan Delay On 15 Seconds 120 Seconds 0 Seconds
The fan’s lag time after the heating or cooling call is initiated when in Fossil Fuel,
Heat Pump, or Cooling operation.
Fan Delay On Elec 0 Seconds 5 Seconds 0 Seconds
The fan’s lag time after the heating or cooling call is initiated when in Electric,
Auxiliary, or Emergency operation.
Fan Delay Off 60 Seconds 120 Seconds 30 Seconds The fan’s lag time after the heating or cooling call is terminated.
Min. Run Time 5 Minutes Stage Delay 3 Minutes The minimum amount of time the system will cycle upon engagement.
Anti Short Cycle 5 Minutes 5 Minutes 0 Minutes
The Anti Short Cycle (ASC) timer represents the minimum amount of time the
system will remain off upon stage down engagement.
Cycle Time 180 Seconds 300 Seconds 60 Seconds Time delay between active heating and cooling transition
Zero Energy
Band Heating
1° F/ 0.5° C 2° F/ 1° C 0.5° F/ 0.3° C
A temperature range between the current temperature and the heating set point,
where heating is not engaged (also called deadband).
Zero Energy
Band Cooling
1° F/ 0.5° C 2° F/ 1° C 0.5° F/ 0.3° C
A temperature range between the current temperature and the cooling set point,
where cooling is not engaged (also called deadband).