Loading ...
Loading ...
Loading ...
KBF / KBF-UL + KMF (E6) 04/2020 page 115/163
17.1 Function of the humidifying and dehumidifying system
Humidifying system
The humidifying and dehumidifying system is located in the humidity generation module. In a cylindrical
container with a volume of approx. 2 liters an electrical resistance heating evaporates water. The water
content is kept exactly at the boiling point, and thus steam can be immediately generated in sufficient
quantity for rapid humidity increases or for compensation of humidity losses, e.g. by door openings. Con-
densation forming on the outer walls of the useable volume is led through a water drain in the outer
chamber into the wastewater can which is pumped off automatically to the wastewater pipe when re-
quired.
Freshwater
You can supply the chamber with freshwater via a water pipe or by manually filling a freshwater can (op-
tion, chap. 19.9). You can mount the can on the rear of the chamber or place it next to the chamber.
In order to ensure accurate humidifying, observe the following points with regard to the
freshwater supply:
Supply pressure 1 to 10 bar when connecting to a water pipe
Water type: deionized (demineralized) water
To ensure humidification during 24 hours even at high humidity set-points with manual
water supply, we recommend filling the freshwater can (option) at the end of each day.
Water intake temperature NOT below +5 °C / 41 °F and not exceeding 40 °C / 104 °F.
BINDER GmbH is NOT responsible for the water quality provided by the customer.
Any problems and malfunctions that might arise following use of water of deviating quality is
excluded from liability by BINDER GmbH.
Automatic freshwater supply via water pipe
With this type of supply, the humidity system is continuously functional.
Manual freshwater supply via freshwater can (option, chap. 19.9)
With this type of supply, the humidity system is functional only if the water can is sufficiently filled. Check
the filling level daily. The water reserve in the can is sufficient for a period, which may last between one
and several days, depending on the humidity demand (entered humidity set-point and number of door
openings).
Wastewater
The condensation water from the interior is collected in an internal can with a volume of approx. 0.5 liters.
It is pumped off via the wastewater pipe.
Dehumidifying system
When the humidity system is activated, the chamber dehumidifies as needed in order to reach the en-
tered humidity set-point inside the control range of temperature and relative humidity (Figure 19).
Dehumidification occurs in case of need by means of defined dew point undershoot of several evapora-
tors of the refrigeration system. The condensate which forms is carried away as wastewater.
If the humidity system is turned off while there are descending temperature curves, then operation of the
refrigeration system may cause dehumidification of the loading material.
For error indications concerning water supply and humidity system, see chap. 11.1.3 and 21.3.
Loading ...
Loading ...
Loading ...