32
ENGLISH
Service unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn8” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF “, “ op1 “ ~ “op7 “ Push the ‘’ button
Target pressure is set
Select the Option using ‘’, ‘’ Button :
“HEAT” , “COOL” Push the ‘’ button
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
!
Setting
Target pressure adjusting
Mode setting method
Mode Low Pressure (kpa) High pressure (kpa)
oFF 804 2990
op1 699 3121
op2 739 2827
op3 843 2696
op4 908 2565
op5 961 2435
op6 1026 2304
op7 804 2990
1,MFL69717904,영영 18. 8. 29. 영영 2:50 Page 32