(3) Multi-unit installation in front and back (unit: in.(mm))
The top and two side surfaces must be exposed to open
space, and barriers on at least one side of the front and back
shall be lower than the outdoor unit.
The installation service spaces shown in the illustrations are based on an air intake temperature of 95°F(35°C)(DB)
for COOL operation. In regions where the air intake temperature regularly exceeds 95°F(35°C)(DB), or if the heat load
of outdoor units is expected to regularly exceed the maximum operating capacity, reserve a larger space than that
indicated at the air intake side of units.
Regarding the required air outlet space, position the units with consideration to the space required for the onsite
refrigerant piping work as well. Consult your dealer if the work conditions do not match those in the drawings.
NOTICE
If drain holes of the outdoor unit are covered by a mounting base or by oor surface, raise
the unit in order to provide a free space of more than 5in.(130mm) under the outdoor unit.
Foundation work
Check the strength and level of the installation ground so that the unit will not cause any
operating vibration or noise after installation.
In accordance with the foundation drawing in the gure, x the unit securely by means of
the foundation bolts.
It is best to screw in the foundation bolts until their length are 0.8in.(20mm) from the
foundation surface.
˃5in.(130mm)
Fix the outdoor unit to the foundation bolts using nuts with resin washers(1) as shown in the gure.
(4) Precautions on installation
Installation instruction
Avoid strong wind blowing directly to the outdoor fan and heat exchanger.If there is no need to install the outdoor
machine in the open space of the building or the enclosure, the following two ways can be used to avoid the fan reversal
or damage caused by strong wind blowing.
(1) Using the windshield
Wind
deector
Fierce wind
(2) Near wall installation
More than 80inch (2000mm)
Fierce wind
Fierce wind
Sketch of machine installation
and strong wind direction
flow out
0.8in. (20mm)
screw nut
foundation bolt M12
fill in mortar
concrete
1
Above 120(3000)