PERFORMANCE DATA
Cooling Capacity Tables
Model No. /
Nominal Capacity
(Btu/h)
Outdoor
Air Temp.
(°F DB)
Indoor Air Temp. °F DB / °F WB
68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
LH367HV
36,000
5 35.66 26.60 1.16 37.87 28.10 1.57 40.09 28.93 1.70 41.69 27.78 1.73 44.52 28.02 1.73 46.73 28.55 1.73
10 35.61 26.80 1.19 37.82 28.31 1.62 40.03 29.14 1.75 41.63 27.99 1.78 44.45 28.22 1.78 46.67 28.76 1.78
15 35.56 26.99 1.22 37.77 28.51 1.66 39.97 29.35 1.80 41.57 28.19 1.83 44.39 28.43 1.83 46.60 28.97 1.82
20 35.51 27.18 1.26 37.71 28.72 1.70 39.92 29.56 1.85 41.51 28.39 1.87 44.33 28.63 1.88 46.53 29.17 1.87
25 35.45 27.38 1.29 37.66 28.92 1.75 39.86 29.77 1.89 41.45 28.59 1.92 44.26 28.83 1.93 46.46 29.38 1.92
30 35.40 27.57 1.32 37.60 29.12 1.79 39.80 29.98 1.94 41.39 28.79 1.97 44.20 29.03 1.97 46.40 29.58 1.97
35 35.35 27.76 1.35 37.55 29.32 1.84 39.74 30.18 1.99 41.33 28.99 2.02 44.13 29.23 2.02 46.33 29.79 2.02
40 35.30 27.95 1.39 37.49 29.52 1.88 39.69 30.39 2.04 41.27 29.19 2.07 44.07 29.43 2.07 46.26 29.99 2.07
45 35.25 28.14 1.42 37.44 29.72 1.92 39.63 30.60 2.08 41.21 29.39 2.12 44.01 29.63 2.12 46.20 30.19 2.11
50 35.20 28.33 1.45 37.39 29.92 1.97 39.57 30.80 2.13 41.15 29.58 2.16 43.94 29.83 2.17 46.13 30.40 2.16
55 35.15 28.51 1.48 37.33 30.12 2.01 39.51 31.01 2.18 41.09 29.78 2.21 43.88 30.03 2.22 46.06 30.60 2.21
60 35.10 28.70 1.52 37.28 30.32 2.06 39.46 31.21 2.23 41.03 29.97 2.26 43.82 30.23 2.27 46.00 30.80 2.26
65 35.05 28.89 1.55 37.22 30.52 2.10 39.40 31.41 2.27 40.97 30.17 2.31 43.75 30.42 2.31 45.93 31.00 2.31
70 34.99 29.07 1.58 37.17 30.71 2.15 39.34 31.61 2.32 40.91 30.36 2.36 43.69 30.62 2.36 45.86 31.20 2.36
75 34.15 28.59 1.68 36.32 30.25 2.21 38.49 31.17 2.39 40.05 29.96 2.43 42.82 30.25 2.45 44.99 30.85 2.46
80 33.31 28.11 1.79 35.47 29.77 2.28 37.64 30.71 2.45 39.20 29.55 2.49 41.96 29.87 2.53 44.12 30.49 2.57
85 32.48 27.59 2.03 34.63 29.27 2.48 36.79 30.24 2.63 38.35 29.11 2.67 41.10 29.46 2.72 43.26 30.10 2.76
90 31.64 27.07 2.28 33.79 28.76 2.68 35.94 29.75 2.81 37.50 28.66 2.85 40.25 29.05 2.90 42.40 29.71 2.96
95 30.74 26.79 2.52 32.88 28.50 2.86 35.02 29.52 2.96 36.00 28.03 2.91 39.30 28.90 3.05 41.44 29.58 3.11
100 29.99 26.07 2.64 32.13
27.78 2.91 34.27 28.82 2.98 35.53 27.60 2.96 38.55 28.27 3.05 40.69 28.97 3.11
105 29.24 25.35 2.77 31.38 27.06 2.96 33.52 28.11 3.00 35.07 27.16 3.01 37.80 27.65 3.05 39.94 28.36 3.11
110 28.49 24.49 2.69 30.63 26.18 2.80 32.77 27.24 2.79 34.32 26.35 2.78 37.05 26.87 2.81 39.20 27.59 2.87
115 27.74 23.75 2.41 29.88 25.45 2.44 32.02 26.52 2.38 33.57 25.68 2.35 36.31 26.23 2.36 38.45 26.96 2.41
118 26.20 22.64 2.14 28.26 24.28 2.11 30.31 25.33 2.01 31.80 24.54 1.97 34.42 25.09 1.96 36.48 25.81 2.01
122 25.69 22.26 2.04 27.71 23.89 1.99 29.74 24.93 1.89 31.21 24.16 1.84 33.80 24.71 1.83 35.82 25.42 1.88
Table 22: LH367HV Ceiling-Concealed Ducted (High Static) System Cooling Capacity Table.
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
PI = Power input (KW). Power input (KW) includes compressor and fan(s).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor
unit. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table rows indicate reference data. When operating at this temperature, these values can
be different if the system is not running consistently.
DUCTED | 41
Product Data
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.