EXTERNAL STATIC PRESSURE
Indoor Units
Setting the External Static Pressure on the Remote Controller
Use this function to set the wind strength for each airflow level.
TEMP
FAN
SPEED
OPER
MODE
To access the controller set mode, press the
and buttons simultaneously
for >three (3)
* External Static Pressure Code: 03
1
Select the desired air flow rate with the
button.
2
Select the desired air flow rate value with
the temperature up), down) button.
* External Static Pressure value range: 0~255
- External Static Pressure value will be displayed
at the upper right-hand section of the screen.
3
Press the button to save / set the chosen
External Static Pressure value.
4
To deactivate the controller set mode, press the
and buttons simultaneously for > three (3) seconds.
- If there is no input (no buttons pressed) for
more than 25 seconds, the controller set mode
will automatically deactivate.
5
OPER
MODE
FAN
SPEED
OPER
MODE
seconds.
(Choose from SLo
→Lo→Med→Hi→Po
.)
The external static pressure must be set by a trained service provider, and it must be set correctly. If the external static pressure is
set incorrectly, the product may malfunction.
Do not alter the external static pressure value that corresponds to each airflow level.
External static pressure values vary according to the model.
When the airflow rate is increased to a higher value, during the external static value setup, the previous airflow value will be stored in
the system memory. (External static pressure values are saved to system memory before the changes are implemented).
DUCTED | 23