1625-2
Users Manual
38
To save a code:
1. Press all 4 keys simultaneously and move central selector from OFF to the desired
measuring mode.
The display shows "C _ _ _".
2. Now enter the CODE number. Any three-digit number can be entered.
Note
Once a CODE has been entered, all subsequently programmed values can
only be changed after entering the CODE number. Once a "CODE" has
been entered, it cannot be erased or changed unless it is known. Be sure to
record your personal "CODE" and store in a safe location.
3. Inputting the code is done by means of the "CHANGE ITEM" and "SELECT" keys.
4. Pressing the "DISPLAY MENU" key completes input.
The CODE is now stored, and the display shows "C ON ".
5. If the display "C ON" is acknowledged by pressing "DISPLAY MENU", the first
parameter of the selected measuring function is displayed and can be changed with
the "CHANGE ITEM" and "SELECT" keys.
a. The changed value is stored by pressing the "DISPLAY MENU" key.
b. Pressing the "START TEST" key exits the setting program.
Note
If the limit values required by regulations are changed incorrect, erroneous
test results may be displayed.
To delete a code:
1. Press all 4 keys simultaneously and move central selector from OFF to any
measuring mode.
The display shows " C _ _ _ ".
2. Now enter the existing CODE number.
3. Inputting the code is done by means of the "CHANGE ITEM" and "SELECT" keys.
Pressing the "DISPLAY MENU" key completes input.