Curve 3: With increasing depth ρE is not decreasing: a strip conductor electrode is
advisable.
As measuring results are often distorted and corrupted, for example, by
underground pieces of metal and underground aquifers, a second
measurement, in which the spike axis is turned by an angle of 90 °, is
always advisable (see graph below).
H
S
E
ES
90°
I
edw022.eps
Measurement of Resistances
Resistance Measurement (R~)
This measuring function determines the ohmic resistance between 0.02 Ω and 300 kΩ.
The measurement is done with ac voltage. For measurements of very low resistances a
compensation of the connecting leads is suggested (see Compensation of Measuring
Lead Resistance).
edw023.eps
Figure 12. Resistance Measurement (R~)
1. Turn central rotary switch to position "R~".
2. Connect instrument as shown in Figure 12.