Electrical Specifications
75
iFlex Probe Specifications
Measuring range
iFlex 1500-12 ......................................................1 to 150 A ac / 10 to 1500 A ac
iFlex 3000-24 ......................................................3 to 300 A ac / 30 to 3000 A ac
iFlex 6000-36 ......................................................6 to 600 A ac / 60 to 6000 A ac
Nondestructive current........................................100 kA (50/60 Hz)
Intrinsic Error at reference condition
[1]
................. ±0.7 % of reading
Accuracy 173x + iFlex
iFlex 1500-12 & iFlex 3000-24 ........................ ±(1 % of reading + 0.02 % of range)
iFlex 6000-36 .................................................. ±(1.5 % of reading + 0.03 % of range)
Temperature Coefficient over operating temperature range
iFlex 1500-12 & iFlex 3000-24 ............................0.05 % of reading / °C (0.09 % of reading / °F)
iFlex 6000-36 ......................................................0.1 % of reading / °C (0.18 % of reading / °F)