FLUKE 1738/B Advanced Three-Phase Power Logger

User Manual for the Fluke 1738/B Advanced Three-Phase Power Logger - Page 76

For 1738/B.

PDF File Manual, 84 pages, Read Online | Download pdf file

1738/B photo
Loading ...
Loading ...
Loading ...
Power Logger
Electrical Specifications
71
Accuracy at Reference Conditions
Parameter Range Maximum Resolution
Intrinsic Accuracy at Reference Conditions
(% of Reading + % of Range)
Voltage 1000 V 0.1 V ±(0.2 % + 0.01 %)
Current
Direct Input
Rogowski Mode
15 mV 0.01 mV ±(0.3 % + 0.02 %)
150 mV 0.1 mV ±(0.3 % + 0.02 %)
Clamp Mode
50 mV 0.01 mV ±(0.2 % + 0.02 %)
500 mV 0.1 mV ±(0.2 % + 0.02 %)
1500 A Flexi
150 A 0.01 A ±(1 % + 0.02 %)
1500 A 0.1 A ±(1 % + 0.02 %)
3000 A Flexi
300 A 1 A ±(1 % + 0.03 %)
3000 A 10 A ±(1 % + 0.03 %)
6000 A Flexi
600 A 1 A ±(1.5 % + 0.03 %)
6000 A 10 A ±(1.5 % + 0.03 %)
40 A
4 A 1 mA (0.7 % + 0.02 %)
40 A 10 mA (0.7 % + 0.02 %)
Frequency 42.5 Hz to 69 Hz 0.01 Hz ±0.1 %
Aux Input ±10 Vdc 0.1 mV ±(0.2 % + 0.02 %)
Voltage Min/Max 1000 V 0.1 V ±(1 % + 0.1 %)
Current Min/Max defined by accessory defined by accessory ±(5 % + 0.2 %)
THD on Voltage 1000 % 0.1 % ±(2.5 % + 0.05 %)
THD on Current 1000 % 0.1 % ±(2.5 % + 0.05 %)
Voltage Harmonic 2 to 50 1000 % 0.1 % ±(2.5 % + 0.05 %)
Unbalance 100 % 0.1 % ±0.15 %