4. PURGINGPROCEDURES,LEAKTEST,ANDTESTRUN
4-2.GASCHARGE
Perform gas charge to unit.
1)Connectgascylindertotheserviceportofstopvalve.
2)Perform airpurge ofthe pipe(or hose) coming fromrefrigerant gas
cylinder.
3)
Replenishspeciedamountofthe refrigerant,whileoperatingtheair
conditioner for cooling.
Note:
In
caseofaddingrefrigerant,complywiththequantityspeciedforthe
refrigeratingcycle.
CAUTION:
When
chargingtherefrigerantsystemwithadditionalrefrigerant,besure
touseliquidrefrigerant.Addinggasrefrigerantmaychangethecomposi-
tion
oftherefrigerantinthesystemandaffectnormaloperationoftheair
conditioner.Also,chargethesystemslowly,otherwisethecompressor
will be locked.
Tomaintainthehighpressureofthegascylinder,warmthegascylinder
withwarmwater[under140°F(40°C)]duringcoldseason.Butneveruse
nakedreorsteam.
Union
Stop valve
Liquid pipe
Union
Union
Union
Indoor
unit
Stop valve with
service port
Gas pipe
Refrigerant gas
cylinder
operating
valve
(forR410A)
Gauge manifold
valve(forR410A)
Chargehose(forR410A)
Refrigerantgascylinder
for R410A with siphon
Electronic scale for
refrigerant charging
Refrigerant(liquid)
Outdoor
unit
4-1.PURGINGPROCEDURESANDLEAK
TEST
1)Remove service port caps fromstop valves on both sides
of refrigerant lines. (The stop valves are fully closed when
shipped.)Leaveclosed.
2)Connectgaugemanifoldtoportsofstopvalves.
3)Evacuate thesystemto 4000 microns from both service
valves.Systemmanifoldgaugesmustnotbeusedtomeasure
vacuum. A micron gauge must be used at all times. Break the
vacuumwithNitrogen(N2)intothedischargeservicevalveto0
PSIG.
4)
Evacuatethesystemto1500microns.Breakthevacuumwith
Nitrogen(N2)intothedischargeservicevalveto0PSIG.
5)Evacuatethesystemto500microns.
6)Close gaugemanifold valves, stopthe pump,and conducta
30 minute rise test.
7)Systemshouldhold500micronsforaminimumof1hour.
8)Fullyopenallstopvalvesonbothsidesofgaspipeandliquid
pipe.Operating withoutfullyopening lowerstheperformance
and this causes trouble.
9)Refer to1-3 andcharge theprescribedamountof additional
refrigerantifneeded.Besuretochargeslowlywithliquidrefrig
-
erant.
Otherwise compositionof therefrigerantin thesystem
maybechangedandaffectperformanceoftheairconditioner.
10)Removegaugemanifoldsandreplaceserviceportcapsand
tighten.
11)
Leaktest
Stop valve
for GAS
Gauge manifold
valve(forR410A)
Compound pressure
gauge(forR410A)
Handle
Low
Handle
High
*Close
*Open
Hexagonal
wrench
*4 to 5 turns
Stop valve
for LIQUID
Pressure gauge
(forR410A)
Precautions when using
the control valve
When attaching the control valve to
theserviceport,valvecoremayde-
form or loosen if excess pressure is
applied.Thismaycausegasleak.
Service port
Charge hose
(forR410A)
Body
Close
Open
Control
valve
A
When attaching the control valve to
the service port, make sure that the
valve core is in closed position, and
then tighten part A. Do not tighten
partAorturnthebodywhenvalve
core is in open position.
Charge hose
(forR410A)
–14.7 psi
[Gauge]
(–0.101
MPa)
Service port cap
(Torque 10 to 13 ft
-Ib, 13.7 to 17.7 N•m,
140 to 180 kgf
•cm)
Stop
valve cap
(Torque 15 to 22 ft-lb,
19.6 to 29.4 N•m, 200
to300kgf▪cm)
Vacuum pump
(forR410A)
Adapter for
preventing
thebackow