4. PURGINGPROCEDURES,LEAKTEST,ANDTESTRUN
4-2.GASCHARGE
Perform gas charge to unit.
1)Connectgascylindertotheserviceportofstopvalve.
2)Perform airpurge ofthe pipe(or hose) coming fromrefrigerant gas
cylinder.
3)
Replenishspeciedamountofthe refrigerant,whileoperatingtheair
conditioner for cooling.
Note:
In
caseofaddingrefrigerant,complywiththequantityspeciedforthe
refrigeratingcycle.
CAUTION:
When
chargingtherefrigerantsystemwithadditionalrefrigerant,besure
touseliquidrefrigerant.Addinggasrefrigerantmaychangethecomposi-
tion
oftherefrigerantinthesystemandaffectnormaloperationoftheair
conditioner.Also,chargethesystemslowly,otherwisethecompressor
will be locked.
Tomaintainthehighpressureofthegascylinder,warmthegascylinder
withwarmwater[under140°F(40°C)]duringcoldseason.Butneveruse
nakedreorsteam.
Union
Stop valve
Liquid pipe
Union
Union
Union
Indoor
unit
Stop valve with
service port
Gas pipe
Refrigerant gas
cylinder
operating
valve
(forR410A)
Gauge manifold
valve(forR410A)
Chargehose(forR410A)
Refrigerantgascylinder
for R410A with siphon
Electronic scale for
refrigerant charging
Refrigerant(liquid)
Outdoor
unit
4-1.PURGINGPROCEDURESANDLEAK
TEST
1)Remove service port caps fromstop valves on both sides
of refrigerant lines. (The stop valves are fully closed when
shipped.)Leaveclosed.
2)Connectgaugemanifoldtoportsofstopvalves.
3)Evacuate thesystemto 4000 microns from both service
valves.Systemmanifoldgaugesmustnotbeusedtomeasure
vacuum. A micron gauge must be used at all times. Break the
vacuumwithNitrogen(N2)intothedischargeservicevalveto0
PSIG.
4)
Evacuatethesystemto1500microns.Breakthevacuumwith
Nitrogen(N2)intothedischargeservicevalveto0PSIG.
5)Evacuatethesystemto500microns.
6)Close gaugemanifold valves, stopthe pump,and conducta
30 minute rise test.
7)Systemshouldhold500micronsforaminimumof1hour.
8)Fullyopenallstopvalvesonbothsidesofgaspipeandliquid
pipe.Operating withoutfullyopening lowerstheperformance
and this causes trouble.
9)Refer to1-3 andcharge theprescribedamountof additional
refrigerantifneeded.Besuretochargeslowlywithliquidrefrig
-
erant.
Otherwise compositionof therefrigerantin thesystem
maybechangedandaffectperformanceoftheairconditioner.
10)Removegaugemanifoldsandreplaceserviceportcapsand
tighten.
11)
Leaktest
Stop valve
for GAS
Gauge manifold
valve(forR410A)
Compound pressure
gauge(forR410A)
Handle
Low
Handle
High
*Close
*Open
Hexagonal
wrench
*4 to 5 turns
Stop valve
for LIQUID
Pressure gauge
(forR410A)
Precautions when using
the control valve
When attaching the control valve to
theserviceport,valvecoremayde-
form or loosen if excess pressure is
applied.Thismaycausegasleak.
Service port
Charge hose
(forR410A)
Body
Close
Open
Control
valve
A
When attaching the control valve to
the service port, make sure that the
valve core is in closed position, and
then tighten part A. Do not tighten
partAorturnthebodywhenvalve
core is in open position.
Charge hose
(forR410A)
–14.7 psi
[Gauge]
(–0.101
MPa)
Service port cap
(Torque 10 to 13 ft
-Ib, 13.7 to 17.7 N•m,
140 to 180 kgf
•cm)
Stop
valve cap
(Torque 15 to 22 ft-lb,
19.6 to 29.4 N•m, 200
to300kgf▪cm)
Vacuum pump
(forR410A)
Adapter for
preventing
thebackow