3. FLARING WORK AND PIPE CONNECTION
3-1. FLARING WORK
1)Cutthecopperpipecorrectlywithpipecutter.(Fig.1,2)
2)Completelyremoveallburrsfromthecutcrosssectionofpipe.(Fig.3)
• Puttheendofthecopperpipetodownwarddirectionasyou
remove burrs in order to avoid to let burrs drop in the piping.
3)Removearenutsattachedtoindoorandoutdoorunits,thenputthem
on pipe having completed burr removal. (Not possible to put them on
afteraringwork.)
4)Flaring work (Fig. 4, 5).Firmly hold copper pipe in thedimension
showninthetable.SelectAinch(mm)fromthetableaccordingtothe
toolyouuse.
5)Check
• ComparethearedworkwithFig.6.
• Ifareisnotedtobedefective,cutoffthearedsectionanddo
aringworkagain.
3-2. PIPE CONNECTION
• Fastenarenutwithatorquewrenchasspeciedinthetable.
• Whenfastenedtootight,arenutmaybrakeafteralongperiodand
cause refrigerant leakage.
Be sure to wrap insulation around the piping. Direct contact with the
barepipingmayresultinburnsorfrostbite.
Outdoor unit connection
Connect
pipes to stop valve pipe joint of the outdoor unit in the same
manner applied for indoor unit.
For tightening, use a torque wrench or spanner and use the same
tightening torque applied for indoor unit.
Fig. 1 Fig. 2
Fig. 3 Fig. 4
Fig. 5 Fig. 6
Tilted
Good
No good
Burr
Copper pipe
Spare reamer
Pipe cutter
Smooth all
around
Even
length
all around
Inside is shin-
ing
withoutany
scratches.
Clutchtype
Flaring tool
Wingnuttype
Copper
pipe
Uneven Burred
3-3. INSULATION AND TAPING
1)Coverpipingjointswithpipecover.
2)Foroutdoorunitside,surelyinsulateeverypipingincludingvalves.
3)Usingpipingtape(E),applytapingstartingfromtheentryofoutdoor
unit.
•
Stoptheendofpipingtape(E)withtape(withadhesiveagentat-
tached).
When piping have to be arranged through above ceiling, closet or
wherethetemperatureandhumidityarehigh,windadditionalcom
-
mercially
soldinsulationtopreventcondensation.
WARNING
When installing the unit, securely connect the refrigerant
pipes before starting the compressor.
Flare nut
Die
Copper
pipe
Pipe diameter
inch(mm)
B
inch(mm)
Ainch(mm) Tightening torque
Clutchtypetool
for
R410A
Clutchtypetool
for R22
Wingnuttypetool
for R22
ft-lb(kgf•cm)
N•m
ø
1/4(6.35) 21/32(17)
0 to 0.02
(0to0.5)
0.04 to 0.06
(1.0to1.5)
0.06 to 0.08
(1.5to2.0)
10to13(140to180) 13.7 to 17.7
ø3/8(9.52) 7/8(22) 25to30(350to420) 34.3 to 41.2
ø1/2(12.7) 1-1/32(26)
0.08 to 0.10
(2.0to2.5)
36to42(500to575) 49.0 to 56.4
ø5/8(15.88) 1-5/32(29) 54to58(750to800) 73.5 to 78.4