2. OUTDOOR UNIT INSTALLATION
2-1. CONNECTING WIRES FOR OUTDOOR UNIT
Be sure to use special circuits for room air conditioner.
Wiring work should be based on applicable technical standards.
Wiring connections should be made following the diagram.
• Screwsshouldbetightenedsotheywon’tloosen.
ELECTRICAL SPECIFICATIONS
OUTDOOR UNIT MXZ-2B20NA
Power
supply(V,PHASE,Hz) 208/230, 1, 60
Max.Fusesize(timedelay)(A)
20
Min.
CircuitAmpacity(A) 15
Fan
motor(F.L.A) 0.96
Compressor
(R.L.A) 10.1
(L.R.A) 15
Control
voltage
Indoorunit-Remotecontroller:(Wireless)
Indoor unit-Outdoor unit : DC12-24V
1)Removetheservicepanel.
2)Fixthe conduit connector to conduit cover withlock nutthen secure it
against unit with screws.
3)Fixtheconduitcovertotheoutdoorunitthensecureitwithscrews.
4)Connectpowersupplycordandindoor/outdoorconnectingwiretotheter
-
minal
block.
(Leavesomeslackinwirestoalloweasierservicing.)
5)Closetheservicepanelsecurely.Makesurethat3-2.PIPECONNECTION
is completed.
Remark:
* A disconnect switch should be required. Check the local code.
** Use a ring tongue terminal in order to connect a ground wire to terminal.
INDOOR UNIT A
Terminal block
Grounding
terminal **
INDOOR UNIT B
Terminal block
Grounding
terminal **
208/230 V AC
1phase 60 Hz
208/230 V AC
1phase 60 Hz
Grounding
terminal **
Grounding
terminal **
Terminal
block 1
Ground
OUTDOOR UNIT
Powersupply208/230VAC
1phase 2wires 60 Hz
Terminal block
UNIT A
Terminal block
UNIT B
Disconnect
switch *
Disconnect
switch *
Connect wires to the matching numbers of terminals.
Be sure to attach each screw to its correspondent
terminal when securing the cord and/or the wire to the
terminal block.
CONNECTING WIRES AND CONNECTING GROUND WIRE
Use solid conductor Min. AWG14 or stranded conductor Min. AWG14.
Use double insulated copper wire with 600 V insulation.
• Usecopperconductorsonly.
* Follow local electrical code.
POWER SUPPLY CABLE AND GROUND WIRE
Use solid or stranded conductor Min. AWG14.
• Usecopperconductorsonly.
* Follow local electrical code.
WARNING:
Usetheindoor/outdoorunitconnectingwirethatmeetstheStandardstoconnecttheindoorandoutdoorunitsandxthewiretotheterminal
blocksecurelysothatnoexternalforceisconveyedtotheconnectingsectionoftheterminalblock.Anincompleteconnectionorxingofthe
wirecouldresultinare.
For future servicing, give extra length to the connecting wires.
Grounding terminal
Conduit
cover
Lock nut
Connector