(2) Lay the wires in the control box through the wire inlet on the
side of the control box.
CAUTION
Do not lay the remote controller wiring or transmission wiring
along with the power supply wiring or other electric wiring in
the same route. Separate the remote controller wiring and
transmission wiring at least 2 in. (50 mm) from the power sup-
ply wiring or other electric wiring, or otherwise malfunctions or
failures may be caused by external electric noise that may
interfere with the remote controller wiring and transmission
wiring.
For the installation and wiring of the remote controller, refer to
the remote controller installation manual provided with the
remote controller.
For power supply wiring, refer to the wiring diagram as well.
Be sure to connect the remote controller wiring and transmis-
sion wiring correctly to the right terminal block.
(3) Follow the instructions below, and lay the wires in the con-
trol box.
Routing wiring
Let the power supply and ground wiring with the conduit pass
through one of the holes on the side cover, and let the transmis-
sion and remote controller wiring with the conduit pass through
another hole.
For protection from uninsulated live parts, thread the high
and low voltage wirings through each of the included insulat-
ing tube and secure it with the included clamp separately.
When using the insulating tube
Cut off the insulation tube at needed length.
WARNING
Trim and lay the wiring neatly and attach the control box
cover securely.
An electric shock or fire may result if the control box cover
catches any wiring or the wires push up the cover.
Low-voltage wiring inlet
Transmission wiring
(Low voltage)
Remote controller wiring
(Low voltage)
Lock nut
(Field supply)
High-voltage wiring inlet
Power supply wiring (High voltage)
Ground wiring (High voltage)
Conduit
(Field supply)
Elbow
(Field supply)
L1 L2
1P2P1F2F1T2T
Fix the wires with
clamp (8) to the
wire fixing bracket
provided to the
control box.
Insert the wires
into the wire clip
provided with the
control box.
PROHIBITED
Never connect the power
supply wiring.
Connection method of remote
controller terminals (X2M)
If stranded wires are used, do
not solder the front end of the
wires.
Twist and fix the upper part so
that the wires will not drop out.
Fix the wires with the
clamp (8) to the wire
fixing bracket provided
to the control box.
Remote controller
wiring (No polarity)
Power supply wiring
(High voltage)
Ground wiring
(High voltage)
Transmission wiring
(No polarity)
Transmission
wiring (Low voltage)
Remote controller
wiring (Low voltage)
Ground
Connection method of
power supply terminals
(X1M)
Insulating tube
(accessory (12))
Conduit
(field supply)
Insulating tube
(accessory (12))
Clamp
(accessory (8))
Wiring
(3 in. (75 mm))
Cut off
01_EN_3P530815-1.fm Page 12 Tuesday, July 10, 2018 6:20 PM