78 | STD. WALL-MOUNTED
Multi F and Multi F MAX Indoor Unit Engineering Manual
MULTI
F
MAX
MULTI
F
Table 37: Multi F Low Wall Console Indoor Units Heating Capacity Table.
Model No. /
Nominal Capacity of
Indoor Unit (Btu/h)
Outdoor Air Temp. Indoor Air Temp. °F DB
°F DB °F WB
61 64 68 70 72 75
TC TC TC TC TC TC
LQN090HV4
9,000
0 -0.4 5.40 5.33 5.28 5.25 5.17 4.95
5 4.5 6.09 6.01 5.96 5.93 5.86 5.63
10 9 6.77 6.70 6.64 6.62 6.54 6.32
17 15 7.68 7.61 7.56 7.53 7.46 7.21
20 19 8.03 7.95 7.90 7.88 7.80 7.53
25 23 8.60 8.52 8.47 8.45 8.37 8.07
30 28 9.09 9.02 8.97 8.94 8.86 8.60
35 32 9.59 9.51 9.46 9.43 9.36 9.13
40 36 10.03 9.95 9.90 9.88 9.80 9.57
45 41 10.47 10.40 10.35 10.32 10.25 10.02
47 43 10.65 10.58 10.53 10.50 10.42 10.20
50 46 10.82 10.75 10.70 10.67 10.60 10.34
55 51 11.11 11.03 10.98 10.96 10.88 10.58
60 56 11.11 11.03 10.98 10.96 10.88 10.62
63 59 11.11 11.03 10.98 10.96 10.88 10.65
68 64 11.11 11.03 10.98 10.96 10.88 10.70
LQN120HV4
12,000
0 -0.4 7.02 6.92 6.86 6.83 6.73 6.43
5 4.5 7.91 7.81 7.75 7.72 7.62 7.32
10 9 8.80 8.70 8.64 8.61 8.51 8.21
17 15 9.99 9.89 9.83 9.79 9.69 9.38
20 19 10.44 10.34 10.27 10.24 10.14 9.79
25 23 11.18 11.08 11.01 10.98 10.88 10.48
30 28 11.82 11.72 11.66 11.62 11.52 11.18
35 32 12.46 12.36 12.30 12.27 12.17 11.87
40 36 13.04 12.94 12.88 12.84 12.74 12.45
45 41 13.62 13.52 13.45 13.42 13.32 13.02
47 43 13.85 13.75 13.68 13.65 13.55 13.25
50 46 14.07 13.97 13.91 13.87 13.77 13.44
55 51 14.44 14.34 14.28 14.24 14.14 13.75
60 56 14.44 14.34 14.28 14.24 14.14 13.81
63 59 14.44 14.34 14.28 14.24 14.14 13.85
68 64 14.44 14.34 14.28 14.24 14.14 13.91
LMQN150HV
15,710
0 -0.4 8.78 8.66 8.58 8.54 8.41 8.04
5 4.5 9.90 9.77 9.69 9.65 9.52 9.15
10 9 11.01 10.89 10.80 10.76 10.64 10.27
17 15 12.49 12.37 12.29 12.25 12.12 11.73
20 19 13.05 12.93 12.84 12.80 12.68 12.25
25 23 13.98 13.85 13.77 13.73 13.61 13.11
30 28 14.78 14.66 14.58 14.53 14.41 13.98
35 32 15.59 15.46 15.38 15.34 15.21 14.84
40 36 16.31 16.18 16.10 16.06 15.94 15.57
45 41 17.03 16.91 16.82 16.78 16.66 16.29
47 43 17.32 17.19 17.11 17.07 16.95 16.58
50 46 17.60 17.47 17.39 17.35 17.22 16.81
55 51 18.06 17.94 17.85 17.81 17.69 17.19
60 56 18.06 17.94 17.85 17.81 17.69 17.27
63 59 18.06 17.94 17.85 17.81 17.69 17.32
68 64 18.06 17.94 17.85 17.81 17.69 17.39
Heating Capacity Table
LOW WALL CONSOLE INDOOR UNITS
TC = Total Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with low length of each outdoor unit. Nominal
heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).