LG Electronics LQN120HV4 LG Air Conditioner Cooling Area, Adjustable Air Direction

User Manual - Page 188

For LQN120HV4.

PDF File Manual, 243 pages, Read Online | Download pdf file

LQN120HV4 photo
Loading ...
Loading ...
Loading ...
External Static Pressure
FOUR-WAY VAHU INDOOR UNITS
Heater Capacity Static Pressure Drop (in. wg)
0 0
3, 5 -0.01
8, 10 -0.02
Table 98: Electric Heater Static Pressure Drop Factors.
Capacity (kBtu/h [tons]) Flow Rate (CFM) Static Pressure Drop (in wg)
18 (1.5)
High (640) -0.04
Middle(580) -0.04
Low (480) -0.04
24 (2.0)
High (710) -0.04
Middle(640) -0.04
Low (480) -0.04
36 (3.0)
High (990) -0.04
Middle(880) -0.04
Low (800) -0.04
Table 99: Down Flow (optional) Static Pressure Drop Factors.
Capacity (kBtu/h [tons]) Flow Rate (CFM) Static Pressure Drop (in wg)
18 (1.5)
High (640) -0.04
Middle(580) -0.04
Low (480) -0.04
24 (2.0)
High (710) -0.04
Middle(640) -0.04
Low (480) -0.04
36 (3.0)
High (990) -0.04
Middle(880) -0.04
Low (800) -0.04
Table 100: Down Flow Air Filter Static Pressure Drop Factors
Heater Capacity (kW) Static Pressure Drop (in. wg)
0 0
3, 5 -0.01
8, 10 -0.01
Table 101: Down Flow Internal Electric Heater Static Pressure Drop.
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
188 | VERTICAL-HORIZONTAL
Multi F and Multi F MAX Indoor Unit Engineering Manual
MULTI
F
MAX
MULTI
F
Loading ...
Loading ...
Loading ...