Connection Name Location Function
CN-POWER AC power supply AC Power line
CN-MOTOR1 Fan motor output Motor output of BLDC
CN_OUT Heater Connection for heater
CN-D/PUMP Drain pump output AC output for drain pump
CN-FLOAT Float switch input Float switch sensing
CN-ZONE Zone controller Zone controller connection
CN-OPTION Optional PCB EPROM Option PCB connection
CN-EXT External ON / OFF controller External ON / OFF controller connection
CN-DISPLAY Display Display of indoor status
CN-CC Dry contact Dry Contact connection
CN-PIPE/OUT (RD) Discharge pipe sensor Pipe out thermistor
CN-LEAK (VI) Refrigerant leak detector Refrigerant leak detector connection
CN-PIPE/IN (WH) Suction pipe sensor Pipe in thermistor
CN-REMO (GN) Wired remote controller Wired remote control connection
CN-ROOM (YL) Room sensor Room air thermistor
CN-DAMPER Damper Controller Damper connection
CN-AIRC Air Cleaner Air Cleaner connection
CN-WF Wifi Wifi Module connection
CN-PTC Auxiliary Heater Auxiliary Heater
Table 108: Wiring Diagram Connections.
Table 109: DIP Switch Settings.
DIP Switch Settings OFF ON Description
SW1 Communication Off (default)
SW2 CYCLE Off (default)
SW3 GROUP Master Slave Group control setting using wired remote controller.
SW4
DRY
CONTACT
Variable Auto
Dry contact mode setting.
1. Variable: Auto/manual mode can be chosen using the wide wired
remote controller or wireless remote controller (factory setting is
the manual mode).
2. Auto: For dry contact, it is always auto mode.
SW5 EXTRA1 Off On
ON: Fan operates continuously.
OFF: Default (Fan does not operate continuously).
SW6 HEATER Off On
ON: Automatic heater operation.
OFF: Default (manual heater operation).
SW7 Off
SW8 Off
To operate the indoor unit without Internal Electric Heater , Dip switch 1, 2, 6, 8 must be set OFF .
To operate the indoor unit with Internal Electric heater , Dip switch 6 must be set ON.
SW6 ON: Automatic Heater operation: Heater operates automatically.
SW6 OFF: Manual Heater operation: Owner ’s involvement is required for on/off operation.
If you operate the indoor unit with Internal Electric heater with Dip switch 5, note the following:
SW5 ON: Fan operates continuously. During defrosting or oil return operation, uninterrupted heating can be attained, as a result of
continuous heater and fan operation.
SW5 OFF: Fan discontinuous operation. There would be a reduction in heating capacity while defrosting or oil return operation.
Wiring Diagram
FOUR-WAY VAHU INDOOR UNITS
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
194 | VERTICAL-HORIZONTAL
Multi F and Multi F MAX Indoor Unit Engineering Manual