LG Electronics LQN120HV4 LG Air Conditioner Cooling Area, Adjustable Air Direction

User Manual - Page 185

For LQN120HV4.

PDF File Manual, 243 pages, Read Online | Download pdf file

LQN120HV4 photo
Loading ...
Loading ...
Loading ...
Table 95: Multi F Vertical-Horizontal Air Handling Indoor Units Heating Capacity Table.
Model No. /
Nominal Capacity
of Indoor Unit
(Btu/h)
Outdoor Air Temp. Indoor Air Temp. °F DB
°F DB °F WB
61 64 68 70 72 75
TC TC TC TC TC TC
LVN181HV4
18,000
0 -0.4 10.29 10.14 10.05 10.00 9.86 9.42
5 4.5 11.59 11.45 11.35 11.30 11.16 10.72
10 9 12.90 12.75 12.66 12.61 12.46 12.03
17 15 14.64 14.49 14.40 14.35 14.20 13.74
20 19 15.29 15.14 15.05 15.00 14.86 14.35
25 23 16.38 16.23 16.14 16.09 15.94 15.36
30 28 17.32 17.17 17.08 17.03 16.88 16.38
35 32 18.26 18.12 18.02 17.97 17.83 17.39
40 36 19.11 18.96 18.86 18.82 18.67 18.24
45 41 19.95 19.81 19.71 19.66 19.52 19.08
47 43 20.29 20.14 20.05 20.00 19.86 19.42
50 46 20.62 20.47 20.37 20.33 20.18 19.69
55 51 21.16 21.01 20.92 20.87 20.72 20.14
60 56 21.16 21.01 20.92 20.87 20.72 20.24
63 59 21.16 21.01 20.92 20.87 20.72 20.29
68 64 21.16 21.01 20.92 20.87 20.72 20.38
LVN241HV4
24,000
0 -0.4 13.89 13.70 13.57 13.50 13.30 12.72
5 4.5 15.65 15.46 15.33 15.26 15.07 14.48
10 9 17.41 17.22 17.09 17.02 16.83 16.24
17 15 19.76 19.57 19.43 19.37 19.17 18.55
20 19 20.64 20.45 20.32 20.25 20.05 19.37
25 23 22.11 21.91 21.78 21.72 21.52 20.74
30 28 23.38 23.18 23.05 22.99 22.79 22.11
35 32 24.65 24.46 24.33 24.26 24.07 23.48
40 36 25.79 25.60 25.47 25.40 25.21 24.62
45 41 26.93 26.74 26.61 26.54 26.35 25.76
47 43 27.39 27.20 27.07 27.00 26.80 26.22
50 46 27.83 27.64 27.51 27.44 27.24 26.58
55 51 28.57 28.37 28.24 28.17 27.98 27.20
60 56 28.57 28.37 28.24 28.17 27.98 27.32
63 59 28.57 28.37 28.24 28.17 27.98 27.39
68 64 28.57 28.37 28.24 28.17 27.98 27.51
FOUR-WAY VAHU INDOOR UNITS
Heating Capacity Table
TC = Total Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
VERTICAL-HORIZONTAL | 185
Vertical-Horizontal Air Handling Unit
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
Loading ...
Loading ...
Loading ...