Model No. /
Nominal Capacity
of Indoor Unit
(Btu/h)
Outdoor Air Temp. Indoor Air Temp. °F DB
°F DB °F WB
61 64 68 70 72 75
TC TC TC TC TC TC
LVN361HV4
36,000
0 -0.4 20.58 20.29 20.10 20.00 19.71 18.84
5 4.5 23.19 22.90 22.71 22.61 22.32 21.45
10 9 25.80 25.51 25.31 25.22 24.93 24.06
17 15 29.28 28.99 28.79 28.70 28.41 27.48
20 19 30.58 30.29 30.10 30.00 29.71 28.70
25 23 32.75 32.46 32.27 32.17 31.88 30.72
30 28 34.64 34.35 34.15 34.06 33.77 32.75
35 32 36.52 36.23 36.04 35.94 35.65 34.78
40 36 38.21 37.92 37.73 37.63 37.34 36.47
45 41 39.90 39.61 39.42 39.32 39.03 38.16
47 43 40.58 40.29 40.10 40.00 39.71 38.84
50 46 41.23 40.94 40.75 40.65 40.36 39.38
55 51 42.32 42.03 41.84 41.74 41.45 40.29
60 56 42.32 42.03 41.84 41.74 41.45 40.47
63 59 42.32 42.03 41.84 41.74 41.45 40.58
68 64 42.32 42.03 41.84 41.74 41.45 40.76
TC = Total Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Table 96: Multi F Vertical-Horizontal Air Handling Indoor Units Heating Capacity Table - continued
FOUR-WAY VAHU INDOOR UNITS
Heating Capacity Table
Due to our policy of continuous product innovation, some specications may change without notication.