Napoleon NZ3000H High Country Series Natural Vent Woodburning Fireplace

User Manual - Page 16

For NZ3000H.

PDF File Manual, 128 pages, Read Online | Download pdf file

NZ3000H photo
Loading ...
Loading ...
Loading ...
W415-1517 / A / 09.02.16
16
EN
4.3 ADDING CHIMNEY SECTIONS
A
dd chimney sections, securely, to the required height.
If the chimney system is enclosed within the attic area, a rafter
radiation shield is required.
The chimney must extend at least 3ft (0.9m) above its point of
contact with the roof and at least 2ft (0.6m) higher than any wall,
roof or building within 10ft (3.1m).
If the chimney extends more than 5ft (1.5m) above the roof,
it must be secured using a roof brace or guide wires.
A
raincap must be installed to avoid internal damage and
corrosion.
Floor, Ceiling
Joist
LIVING SPACE
Framed
Enclosure
2” (50.8mm)
clearance from
chimney to
combustible wall
Chimney Lengths
Ceiling Joist
Chimney must be
totally enclosed
when passing
through living space
with a minimum 2”
(50.8mm) clearance
to combustibles.
3 ft.
(0.9m)
MIN.
2ft.
(0.6m)
59.2A
3 ft. (0.9m)
MIN.
2ft.
(0.6m)
10 ft.
(3.1m)
Loading ...
Loading ...
Loading ...