Page16
Version1.0Aug2018
After the water heater is installed,the appliance and its gas connection, including factory connections, MUST be
leak‐testedatnormaloperatingpressure.
Warning!
NEVERuseanopenflametotestforgasleak!
Turnonthegasservicevalve.
Usesoapywatertotestforleakageatallgasconnectionsandfittings.Ifbubblesareseen,itindicatesthere
isaleakandMUSTberectified–seeFigure17.
HighAltitudeInstallation
Thewaterheaterissuitableforinstallationupto2000ft(600m) above sea level. The input rating of this water
heaterisbasedonsealeveloperation.Athigherelevations,theactualinputratemaybelowerthanthevaluelisted
inproductdatalabel.
For installation above 2000ft (600m) elevation, contact a qualifiedservicetechniciantomakeproperaltitude
adjustments.
Warning!
Do NOT install the water heater at elevations above 2000ft (600m).PleasecontactONSENcustomerservicefor
futureadvice.
HotandColdSupplyLineInsulation
Suitablepipeinsulationand/orelectricheat‐tracingshouldbeusedtopreventwaterinthepipesfromfreezing.
Ifwaterinthepipingisfrozen,thewaterheaterwillmalfunction.
BothHotandColdwaterlinesshouldbeinsulatedforprotectioninareaspronetofreezingconditions–seeFigure
18.
Figure17
Figure 18