26
System Control Board
The generator control board, located inside the generator,
under the roof, is shown below. Brief descriptions of the
controls used during installation are:
A
- Menu/Programming Navigation Buttons — See
Menu section for details
B
- Mini USB Port — Authorized Dealer Service Use
Only
C
- Generator Operation Control Buttons —
•“AUTONormal operating position. Press and hold
button to put unit into Automatic mode. If an utility
power outage is sensed, the system will start the
generator. When utility power is restored, auto lets
the engine stabilize internal temperatures, shuts o
the generator, and waits for the next utility outage.
•“OFFTurns o running generator, prevents unit from
starting, and resets any detected faults.
OFF must be pressed and held for more than 5 seconds in
order to reset service codes.
•“MANUALUsed to manually start the generator.
*
- AUTO” LED — LED will light when unit is placed into
Auto mode. LED will blink if exercise cycle is not set
or set to OFF.
D
15 Amp Fuse — Protects the home generator DC
control circuits. If the fuse has ‘blown’ (melted open)
or was removed, the engine cannot crank or start.
Replace the fuse using only an identical ATO 15A
fuse. One spare fuse is supplied with the unit.
E
- CoverThis protective cover must be opened to
access the fuse and the USB port.
F
- Digital Display — Displays generator mode, menu
options, service codes, and service engine indicators
More information may be found in Controls in the
operator’s manual.
MENU
ESC
AUTO OFF
MANUAL
A
B
C
D
F
E
Not for
Reproduction
Loading ...
Loading ...
Loading ...