Briggs & Stratton 040684 Power Protect 10kW Home Standby Generator

Installation and Operation Manual - Page 24

For 040684.

PDF File Manual, 180 pages, Read Online | Download pdf file

040684 photo
Loading ...
Loading ...
Loading ...
24
Communication Connections
Connect the applicable communication leads to the
automatic transfer switch as shown in the table below.
* Metric system rounded for simplicity
Pin
Number
Description Wire Type Connect To Notes
1 Normally Open
18 AWG [1 mm²] twisted pair conductors no longer
than 61 m, 300V, 90°C copper wire
For Optional Alarm
2 Common
18 AWG [1 mm²] twisted pair conductors no longer
than 61 m, 300V, 90°C copper wire
For Optional Alarm
3 Normally Closed
18 AWG [1 mm²] twisted pair conductors no longer
than 61 m, 300V, 90°C copper wire
For Optional Alarm
4
Transfer Switch
Communication
18 AWG [1 mm²] twisted pair conductors no longer
than 61 m, 300V, 90°C copper wire
4 (T/R) on transfer switch
board
Must Connect
5
Transfer Switch
Communication Ground
18 AWG [1 mm²] twisted pair conductors no longer
than 61 m, 300V, 90°C copper wire
5 (GND) Ground on transfer
switch board
Must Connect
6 +LED
18 AWG [1 mm²] twisted pair conductors no longer
than 61 m, 300V, 90°C copper wire
Red wire on fault indicator
plate
For Optional Fault
Indication
7 Ground
18 AWG [1 mm²] twisted pair conductors no longer
than 61 m, 300V, 90°C copper wire
Black wire on fault indicator
plate
For Optional Fault
Indication Ground
8 Not Used N/A N/A N/A
25 Utility 14 AWG [2.5 mm²] minimum 300v wire Transfer Switch Utility Must Connect
26 Utility 14 AWG [2.5 mm²] minimum 300v wire Transfer Switch Utility Must Connect
Generator AC Connection System
A single-phase, three-wire AC connection system is used
in the home generator. The stator assembly consists of
a pair of stationary windings with two leads brought out
of each winding. The junction of leads 22 and 33 forms
the neutral lead, as shown schematically and as a wiring
diagram. A complete schematic and wiring diagram can be
found later in this manual.
NOTICE
Neutral is not bonded to ground at generator.
NOTICE Generator must be used with only an UL listed
transfer switch that is compatible with the generator.
240V
120V
120V
Power Winding
11
44
Neutral
Circuit
Breaker
33
22
Circuit
Breaker
33
22
11
0
44
N
L1
L2
Not for
Reproduction