LG LMQN150HV Air Conditioner Cooling Area, Adjustable Air Direction

User Manual - Page 22

For LMQN150HV.

PDF File Manual, 243 pages, Read Online | Download pdf file

LMQN150HV photo
Loading ...
Loading ...
Loading ...
Mounting the Installation Plate
The mounting wall must be strong and solid enough to protect the unit from vibration.
Mount the installation plate on the wall using the Type “A” screws. If mounting the unit on concrete, consider using anchor bolts.
Always mount the installation plate horizontally. Measure the wall and mark the centerline using thread and a level.
ART COOL MIRROR INDOOR UNITS
Installation and Best Layout Practices
DANGER
To avoid the possibility of re, do not install the unit in an area where combustible gas will generate, ow, stagnate, or leak. Failure to do so will
cause serious bodily injury or death. Before beginning installation, read the safety summary at the beginning of this manual.
Select a location for installing the wall-mounted indoor unit (IDU) that meets the following conditions:
Where there is enough structural strength to bear the weight of the unit
Where air circulation will not be blocked
Where noise prevention is taken into consideration
Ensure there is sufficient space from the ceiling and floor
Locate the indoor unit in a location where it can be easily connected to the outdoor unit/branch distribution unit
Include space for drainage to ensure condensate flows properly out of the unit when it is in cooling mode
Use a level indicator to ensure the unit is installed on a level plane
Note:
The unit will be damaged, will malfunction, and/or will not operate as designed if installed in any of the following conditions:
Do not install the unit where it will be subjected to direct thermal radiation from other heat sources.
Do not install the unit in an area where combustible gas will generate, flow, stagnate, or leak.
Do not install the unit in a location where acidic solution and spray (sulfur) are often used.
Do not use the unit in environments where oil, steam, or sulfuric gas are present.
Do not install additional ventilation products on the chassis of the unit.
Do not install the unit near high-frequency generator sources.
Do not install the unit near a doorway.
>4 inches
Recommended height
>6-1/2 feet from floor
>4 inches
≥5 inches
Figure 10:Minimum Clearance Requirements.
Installing in an Area Exposed to Unconditioned Air
In some installation applications, areas (floors, walls) in some rooms
will be exposed to unconditioned air (room will be above or next to
an unheated garage or storeroom). To countermeasure:
Verify that carpet is or will be installed (carpet will increase the
temperature by three degrees).
Add insulation between the floor joists.
Install radiant heat or another type of heating system to the floor.
Required Clearances
Figure 10 shows required clearance distances around a typical
installed wall-mounted unit.
Indoor units (IDUs) must not be placed in an environment where the IDUs will be exposed to harmful volatile organic compounds (VOCs)
or in environments where there is improper air make up or supply or inadequate ventilation. If there are concerns about VOCs in the envi-
ronment where the IDUs are installed, proper air make up or supply and/or adequate ventilation must be provided. Additionally, in buildings
where IDUs will be exposed to VOCs, consider a third party factory-applied epoxy coating to the fan coils for each IDU where the entire coil
is dipped, not sprayed.
If the unit is installed near a body of water, the installation parts are at risk of corroding. Appropriate anti-corrosion methods must be taken
for the unit and all installation parts.
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
22 | ART COOL MIRROR