FOUR-WAY VAHU INDOOR UNITS
Installation and Best Layout Practices
Indoor Unit Terminal Block
1(L1 )2(L2)
GND
3
Branch Distribution Unit
GRN /
YLW
BR
BL
RD
CN-REMO
YL
RD BK
Comm.
12V
Power
Ground
Figure 269:PZCWRC1 LG Wired Remote Extension Cable.
Controller Options
Vertical-Horizontal Air Handling indoor units can be used with many LG-supplied wired controllers (sold separately). The wireless handheld
controller (Model No. PQWRHQ0FDB) is also an optional accessory with use of the wired controller.
Verify the connectors are properly inserted.
C/BOX Cable (Plug type)
Extension cable
To Indoor Unit
CN-REMO
Terminal
TEMP
FAN
SPEED
OPER
MODE
Figure 270:Wired Controller Connection on the Indoor Unit Terminal Block.
When using eld-supplied controller cable, make sure to connect
the yellow to yellow (communications wire), red to red (12V power
wire), and black to black (ground wire) terminals from the remote
controller to the indoor unit terminal blocks.
Wired Controller Connections
Controllers can connect to the indoor unit in one of two different ways.
1. LG Wired Remote Extension Cable with Molex plug (PZCWRC1; sold separately) that connects to the CN-REMO terminal on the indoor
unit PCB.
2. Field-supplied controller cable that connects to the indoor unit terminal block (must be at least UL2547 or UL1007, 22 AWG, two-core,
one-shield core, at least FT-6 rated if local electric and building codes require plenum cable usage).
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
202 | VERTICAL-HORIZONTAL
Multi F and Multi F MAX Indoor Unit Engineering Manual