LG LMQN150HV Air Conditioner Cooling Area, Adjustable Air Direction

User Manual - Page 122

For LMQN150HV.

PDF File Manual, 243 pages, Read Online | Download pdf file

LMQN150HV photo
Loading ...
Loading ...
Loading ...
MULTI
F
MAX
MULTI
F
Table 59:Multi F Ceiling-Concealed Duct (High Static) Indoor Units Heating Capacity Table.
Model No. /
Nominal Capacity
of Indoor Unit
(Btu/h)
Outdoor Air Temp. Indoor Air Temp. °F DB
°F DB °F WB
61 64 68 70 72 75
TC TC TC TC TC TC
LHN248HV
24,000
0 -0.4 13.89 13.70 13.57 13.50 13.30 12.72
5 4.5 15.65 15.46 15.33 15.26 15.07 14.48
10 9 17.41 17.22 17.09 17.02 16.83 16.24
17 15 19.76 19.57 19.43 19.37 19.17 18.55
20 19 20.64 20.45 20.32 20.25 20.05 19.37
25 23 22.11 21.91 21.78 21.72 21.52 20.74
30 28 23.38 23.18 23.05 22.99 22.79 22.11
35 32 24.65 24.46 24.33 24.26 24.07 23.48
40 36 25.79 25.60 25.47 25.40 25.21 24.62
45 41 26.93 26.74 26.61 26.54 26.35 25.76
47 43 27.39 27.20 27.07 27.00 26.80 26.22
50 46 27.83 27.64 27.51 27.44 27.24 26.58
55 51 28.57 28.37 28.24 28.17 27.98 27.20
60 56 28.57 28.37 28.24 28.17 27.98 27.32
63 59 28.57 28.37 28.24 28.17 27.98 27.39
68 64 28.57 28.37 28.24 28.17 27.98 27.51
LHN368HV
36,000
0 -0.4 20.58 20.29 20.10 20.00 19.71 18.84
5 4.5 23.19 22.90 22.71 22.61 22.32 21.45
10 9 25.80 25.51 25.31 25.22 24.93 24.06
17 15 29.28 28.99 28.79 28.70 28.41 27.48
20 19 30.58 30.29 30.10 30.00 29.71 28.70
25 23 32.75 32.46 32.27 32.17 31.88 30.72
30 28 34.64 34.35 34.15 34.06 33.77 32.75
35 32 36.52 36.23 36.04 35.94 35.65 34.78
40 36 38.21 37.92 37.73 37.63 37.34 36.47
45 41 39.90 39.61 39.42 39.32 39.03 38.16
47 43 40.58 40.29 40.10 40.00 39.71 38.84
50 46 41.23 40.94 40.75 40.65 40.36 39.38
55 51 42.32 42.03 41.84 41.74 41.45 40.29
60 56 42.32 42.03 41.84 41.74 41.45 40.47
63 59 42.32 42.03 41.84 41.74 41.45 40.58
68 64 42.32 42.03 41.84 41.74 41.45 40.76
Heating Capacity Table
DUCT (HIGH STATIC) INDOOR UNITS
TC = Total Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
122 | DUCT (HIGH STATIC)